31
DC SSR Driver (voltage pulse)
• The non-isolated DC output is used to drive an external load-handling
device such as Solid-State Relay(SSR) or Solid-State Contactor(SSC).
• The total current drawn should be within the allowed value.
• Make sure the polarity is correct.
• Set the proportional time cycle parameter, “
TC
” to 1 sec. or more.
4 to 20mA DC
• The output is a non-isolated analog signal used to drive a variety of
output devices such as SCRs and valve actuators.
• The load resistance must be less than 600
Ω
.
• Make sure the polarity is correct.
• The proportional time cycle parameter, “
TC
” is set to 0, and is not
displayed on the programming menu.
• Not available on CN4321.
Wiring Alarms
• Make sure the load does not exceed the rated capacity of the relay.
• Several types of alarm configurations can be programmed and does
not require a change in the wiring. Refer to parameters
AL
,
AH
,
P-AH
,
P-AL
,
P-An
.