78
somewhere between 0% and 50% of the Heating Proportional band.
To establish an Overlap, “db” is set somewhere between -50% and
0% of the Heating Proportional Band.
8. Manually fine-tune the parameters, “CooL” and “db”, until just the
right amount of cooling is achieved. Refer to the programming
section for more details on these parameters.
Heating Side
Cooling SIde
Heating Proportional Band
Cooling Proportional Band
[P/2]
[P/2 COOL]
I
I (same as for heating)
D
D (same as for heating)