Parameter
Range
Description
Default
DSP
settings settings
P-SU
-1999 - 9999
Upper range of input
100%FS dSP3-8
P-dP
0 - 2
Decimal point position
0
dSP3-16
P-AH
0 - 11
Alarm Type 1 code
5
dSP3-32
P-AL
*
0 - 15
Alarm Type 2 code
9
dSP3-64
PVOF
-10 - 10%FS
PV offset
0
dSP3-128
SVOF
-50 - 50%FS
SV offset
0
dSP4-1
P-F
°
C/
°
F
°C/°F selection
†
dSP4-2
STAT
--
Ramp/soak status
oFF
dSP4-4
SV-1
0 - 100%FS
1st setpoint
0%FS
dSP4-8
TM1r
0 - 99hr 59min
1st ramping time
0.00
dSP4-16
TM1S 0 - 99hr 59min
1st soaking time
0.00
dSP4-32
SV-2
0 - 100%FS
2nd setpoint
0%FS
dSP4-64
TM2r
0 - 99hr 59min
2nd ramping time
0.00
dSP4-128
TM2S 0 - 99hr 59min
2nd soaking time
0.00
dSP5-1
SV-3
0 - 100%FS
3rd setpoint
0%FS
dSP5-2
TM3r
0 - 99hr 59min
3rd ramping time
0.00
dSP5-4
TM3S 0 - 99hr 59min
3rd soaking time
0.00
dSP5-8
SV-4
0 - 100%FS
4th setpoint
0%FS
dSP5-16
TM4r
0 - 99hr 59min
4th ramping time
0.00
dSP5-32
TM4S 0 - 99hr 59min
4th soaking time
0.00
dSP5-64
MOD
0-15
Ramp/soak Mode code
0
dSP5-128
80
Summary of Contents for CN4321
Page 33: ...32 SYSTEM WIRING DIAGRAMS Example 1 Example 2...
Page 45: ...44 Deadband Overlap...
Page 48: ...47 Table of Input Type Codes...
Page 50: ...49...
Page 53: ...52 Table of Alarm Action Type Codes CN4321...
Page 54: ...53 Table of Alarm Action Type Codes CN4431...
Page 59: ...58 Table of Output Type Codes...