P,I,D= 0: On/Off action (without dead band) for heating and cooling
I,D= 0: Proportional action
_________________________________________________________
Proportional cycle
1-150 sec, for relay contact output and DC SSR
driver output only
_________________________________________________________
Hysteresis width
On/Off action for heating and cooling: 0.5% FS
On/Off action for cooling: 0.5% FS
_________________________________________________________
Anti-reset wind-up
0-100% FS, setting in 1 E.U. steps, auto-setting
with auto-tuning
_________________________________________________________
Overlap/dead band
±50% of heating proportional band
_________________________________________________________
Input sampling cycle
0.5 sec
_________________________________________________________
OUTPUT
(Single Output)
_________________________________________________________
Control output
One of the following three types is selected:
(1) Relay contact (SPDT)
220V AC/30V DC, 3A (resistive load)
Mechanical life: 10
7
times (under no load)
Electrical life: 10
5
times (under the rated load)
(2) DC SSR driver (voltage pulse):
15-30V DC at ON/0.5V DC or less at OFF.
Current: 60mA or less.
(3) 4-20mA DC:
Allowable load resistance– 600
Ω
or less.
_________________________________________________________