53
MOD Power on start Output on END
Output on OFF Repeat function
0
No
Continue controlling
Continue controlling
No
1
No
Continue controlling
Continue controlling
Yes
2
No
Continue controlling
Stand-by mode
No
3
No
Continue controlling
Stand-by mode
Yes
4
No
Stand-by mode
Continue controlling
No
5
No
Stand-by mode
Continue controlling
Yes
6
No
Stand-by mode
Stand-by mode
No
7
No
Stand-by mode
Stand-by mode
Yes
8
Yes
Continue controlling
Continue controlling
No
9
Yes
Continue controlling
Continue controlling
Yes
10
Yes
Continue controlling
Stand-by mode
No
11
Yes
Continue controlling
Stand-by mode
Yes
12
Yes
Stand-by mode
Continue controlling
No
13
Yes
Stand-by mode
Continue controlling
Yes
14
Yes
Stand-by mode
Stand-by mode
No
15
Yes
Stand-by mode
Stand-by mode
Yes
1. Power on Start: Program starts from the current PV value.
2. Output on END: Output condition at the end of the program (ProG=End)
3. Output on OFF:
Output condition when program is terminated (ProG=oFF)
4. Repeat function: Ramp-soak program operates repeatedly.
If the repeat function is off, the SV value on the last step is
maintained.
Stand-by mode:
Output -3%, Alarm off.
Continue Controlling:
When program ends (End), control is at the SV value on
the last step. When program is terminated (oFF), control is at the main SV value.
Table of Ramp/Soak Modes