PLATINUM
TM
Series Controllers User
’s
Guide
M5451
Omega Engineering | www.omega.com
76
Specifications
Table 8
–
Ranges and Accuracies for Supported Inputs
Input Type
Description
Range
Accuracy
Process
Process Voltage
+/- 50 mV, +/-100 mV, +/-1, +/-
10 Vdc
0.03% FS
Process
Process Current
Scalable within 0 to 24 mA
0.03% FS
J Type T/C
Iron-Constantan
-210 to 1200°C / -346 to 2192°F
0.4°C / 0.7°F
K Type T/C
CHROMEGA®-ALOMEGA®
-270 to -160°C / -454 to -256°F
1.0°C / 1.8°F
-160 to -1372°C / -256 to 2502°F 0.4°C / 0.7°F
T Type T/C
Copper-Constantan
-270 to -190°C / -454 to -310°F
1.0°C / 1.8°F
-190 to 400°C / -310 to 752°F
0.4°C / 0.7°F
E Type T/C
CHROMEGA®-Constantan
-270 to -220°C / -454 to -364°F
1.0°C / 1.8°F
-220 to 1000°C / -364 to 1832°F
0.4°C / 0.7°F
R Type T/C
Pt/13%Rh-Pt
-50 to 40°C / -58 to 104°F
1.0°C / 1.8°F
40 to 1788°C / 104 to 3250°F
0.5°C / 0.9°F
S Type T/C
Pt/10%Rh-Pt
-50 to 100°C / -58 to 212°F
1.0°C / 1.8°F
100 to1768°C / 212 to 3214°F
0.5°C / 0.9°F
B Type T/C
30%Rh-Pt/6%Rh-Pt
100 to 640°C / 212 to 1184°F
1.0°C / 1.8°F
640 to 1820°C / 1184 to 3308°F
0.5°C / 0.9°F
C Type T/C
5%Re-W/26%Re-W
0 to 2320°C / 32 to 4208°F
0.4°C / 0.7°F
N Type T/C
Nicrosil-Nisil
-250 to -100°C / -418 to -148°F
1.0°C / 1.8°F
-100 to 1300°C / -148 to 2372°F
0.4°C / 0.7°F
RTD
Pt, 0.00385, 100
Ω
, 500
Ω
, 1000
Ω
-200 to 850°C / -328 to 1562°F
0.3°C / 0.5°F
RTD
Pt, 0.003916, 100
Ω
-200 to 660°C / -328 to 1220°F
0.3°C / 0.5°F
RTD
Pt, 0.00392, 100
Ω
-200 to 660°C / -328 to 1220°F
0.3°C / 0.5°F
Thermistor
2252
Ω
-40 to 120C / -40 to 248F
0.2°C / 0.35°F
Thermistor
5K
Ω
-30 to 140C / -22 to 284F
0.2°C / 0.35°F
Thermistor
10K
Ω
-20 to 150C / -4 to 302F
0.2°C / 0.35°F
Table 9
–
Error Code Descriptions
Code
Error Code Descriptions
Code
Error Code Descriptions
E001
File not found during load operation
E010
Communications device not ready (USB,
Serial, etc.)
E002
Bad file format during load operation
E011
Communications install error
E003
File read error during load operation
E012
Failed attempt to open a
communications device
E004
File write error during save operation E013
Failed attempt to read from a
communications device
E005
Device not found for read or write
operation
E014
Failed attempt to write to a
communications device
E006
Loop break timeout
E015
Bad reboot, attempt to reboot from an
unknown source
E007
Autotune timeout
E016
Can’t auto tune because input signal is
on wrong side of setpoint
E008
Ramp and Soak program tracking
error
E017
Signal too unstable to perform autotune
E009
Input signal out of range
E01D
Autotune measurement error