PLATINUM
TM
Series Controllers User
’s
Guide
M5451
Omega Engineering | www.omega.com
12
Wiring Instructions
3.3
Connecting Inputs
The 10-pin universal input connector assignments are summarized in
Table 1
.
Table 2
provides detail for
the specific types of sensors supported. All sensor selections are firmware-controlled (see
) and no jumper settings are required when switching from one type of sensor
to another.
Figure 5
provides more detail for connecting RTD sensors.
Figure 6
shows the connection
scheme for process current input with either internal or external excitation.
Figure 7
shows the
connections for Single Ended and Differential input voltages.
Table 1
–
10-Pin Input Connector Wiring Summary
Pin No.
Code
Description
1
ARTN
Analog return signal (analog ground) for sensors and remote Setpoint
2
AIN+
Analog positive input
3
AIN-
Analog negative input
4
APWR
Analog power currently only used for 4-wire RTDs
5
AUX
Auxiliary analog input for remote Setpoint
6
EXCT
Excitation voltage output referenced to ISO GND
7
DIN
Digital input signal (latch reset, etc.), Positive at > 2.5V, ref. to ISO GND
8
ISO GND Isolated ground for serial communications, excitation, and digital input
9
RX/A
Serial communications receive
10
TX/B
Serial communications transmit
Table 2
–
Interfacing Sensors to the Input Connector
Pin
Number
Diff
Voltage
Process
Voltage
Process
Current
Thermo-
couple
2-Wire
RTD
3-Wire
RTD
4-Wire
RTD
Thermistor
Remote
Setpoint
1
Rtn
**
RTD2-
RTD2+
Rtn(*)
2
Vin +/-
Vin +/-
I+
T/C+
RTD1+
RTD1+
RTD1+
TH+
3
Vd +/-
I-
T/C-
RTD2-
TH-
4
RTD1-
RTD1-
RTD1-
5
V/I In
*For Remote Setpoint with an RTD, Pin 1 on the Output Connector must be used for the RtN instead of Pin 1 on the
Input Connector. Remote Setpoint is not available if using an RTD sensor and have an SPDT (Type 3) Output
installed.
** Requires external connection to pin 4