Series Controllers User
’s
Guide
M5451
Omega Engineering | www.omega.com
25
Complete Menu Structure
Level
2
Level
3
Level
4
Level
5
Level
6
Notes
No
Multi-Ramp/Soak Mode off
yES
Multi-Ramp/Soak Mode on
RMt
M.RMP
on, start with digital input
____
Select program (number for
M.RMP
program), options 1
–
99
Guaranteed Ramp: soak SP must be reached in ramp time
SoAk
Guaranteed Soak: soak time always preserved
CYCL
Guaran
teed Cycle: ramp can extend but cycle time can’t
Note: tIM.F does not appear for 6 digit display that use a HH:MM:SS format
“Minutes : Seconds” default time format for R/S programs
HH:MM
“Hours : Minutes” default time format for R/S programs
StOP
Stop running at the end of the program
HOLd
Continue to hold at the last soak setpoint at program end
LINk
____
Start the specified ramp & soak program at program end
1 to 8 Ramp/Soak segments (8 each, 16 total)
____
Select segment number to edit, entry replaces # below
____
Time for Ramp number, default = 10
MRE.#
oFF
Ramp events on for this segment
oN
Ramp events off for this segment
MSP.#
____
Setpoint value for Soak number
MSt.#
____
Time for Soak number, default = 10
MSE.#
oFF
Soak events off for this segment
oN
Soak events on for this segment
5.3
Operating Mode Menu (oPER)
The following table maps the Operating Mode (
) navigation:
Level
2
Level
3
Level
4
Notes
Normal Run Mode, process value displayed,
SP1
in optional secondary display
____
Shortcut to change Setpoint 1, current Setpoint 1 value in main display
____
Shortcut to change Setpoint 2, current Setpoint 2 value in main display
____
Manual Mode, the RIGHT and LEFT buttons control output, displays
M##.#
M.INP
____
Manual Mode, the RIGHT and LEFT buttons simulate the input for testing
Pause and hold at current process value, display flashes
Stop controlling, turn off outputs, process value rotating flash, Alarms remain
also allows digital input reset
Displays the lowest input reading since the
VALy
was last cleared
Displays the highest input reading since the
PEAk
was last cleared