Reference Section: Programming Mode (PRoG)
7.4.1
Output Channel Mode (PRoG > oUt1
–
oUt6 > ModE)
Select Output Channel Mode (
ModE
) to configure the specified output.
Navigate to the desired setting. Settings include the following:
oFF
–
Turn off the output channel
(factory default)
PId
–
Set the output to Proportional-Integral-Derivative (PID) Control Mode
oN.oF
–
Set the output to On/Off Control Mode
ALM.1
–
Set the output to be an Alarm using the
ALM.1
configuration
ALM.2
–
Set the output to be an Alarm using the
ALM.2
configuration
RtRN
–
Set up the output for Retransmission
RE.oN
–
Turn on the output during Ramp events
SE.oN
–
Turn on the output during Soak events
Select the indicated setting.
7.4.1.1
Turn Off Output Channel (PRoG > oUt1
–
oUt6 >
ModE > oFF)
Turn off this output (
oFF
).
7.4.1.2
PID Control Mode (PRoG > oUt1
–
oUt6 > ModE >
PId)
Select PID Control Mode (
PId
) for this output (factory default). PID parameters are
set outside the specific output submenus, as more than one output can be used for
PID control at a time. See
7.5 PID Configuration (PRoG > PID)
7.4.1.3
PID 2 Control Mode (PRoG > oUt1
–
oUt6 > ModE
> PId.2)
Select PID Control Mode (
PId.2
) for this output. PID.2 parameters are set outside
the specific output submenus, as more than one output can be used for PID.2
control at a time. See
7.5 PID Configuration (PRoG > PID)
7.4.1.4
On/Off Control Mode (PRoG > oUt1
–
oUt6 >
ModE > oN.oF)
Select On/Off Control Mode (
oN.oF
) for this output. More than one output can be
set up for
oN.oF
control. For Heat / Cool control set the output connected to the
heater with
ACtN
equal to
RVRS
and the output connected to the cooling device
with
ACtN
set to
dRCt
.