22
Input Type (Process)
ENTER INPUT TYPE MENU:
Press
a
1)
Press
a
, if necessary, until
CNFG
prompt appears.
Press
d
2)
Display advance to
INPT
Input Menu.
Press
d
3)
Display flashes
T.ç
,
RTD
or
PROC
(Thermocouple, RTD or
Process). If the displayed input type is
PROC
, press
a
to skip to
step 6 (
PROC
stops flashing).
PROCESS SUBMENU:
Press
b
4)
Scroll through the available selection to
PROC
(flashing).
Press
d
5)
Display shows
STRD
stored message momentarily and then
PROC
(not flashing).
Press
d
6)
Display flashes previous Process type selection. i.e.
0-10
(see below for Process types selection).
Press
b
7)
Scroll through the available Process types to the selection of
your choice.
Press
d
8)
Display shows
STRD
stored message and then advances to
RDG
Reading Configuration Menu.
Process Types:
100 mV 1 V
10 V
0 – 20 mA
Display:
0-0.1
0-1.0
0-10
0-20
For 4-20 mA Input select 0-20 mA and adjust the Input/Reading accordingly.
To adjust 4-20 mA input, see example under Input/Reading Submenu.
3.2.5 Reading Configuration Menu
Figure 3.4 Flow Chart for Reading Configuration Menu
It
is required that you put the controller in the Standby Mode for any
configuration change other than Set Points & Alarms.
Summary of Contents for CNi16A
Page 62: ...4 1 1 8 DIN Mounting 58...
Page 63: ...4 2 1 16 DIN Mounting 59...
Page 69: ...NOTES...
Page 70: ...NOTES...
Page 71: ...NOTES...