57
EXCITATION
(optional in place of Communication)
24 Vdc @ 25 mA
Not available for Low Power Option
INSULATION
Power to Input/Output
2300 Vac per 1 min. test
1500 Vac per 1 min. test
(Low Voltage/Power Option)
Power to Relays/SSR Outputs
2300 Vac per 1 min. test
Relays/SSR to Relay/SSR Outputs
2300 Vac per 1 min. test
RS232/485 to Inputs/Outputs
500 Vac per 1 min. test
Approvals
FM, UL, C-UL, and
see CE Approval Section
GENERAL
Line Voltage/Power
90-240 Vac +/-10%, 50-400 Hz
*
110-375 Vdc, equivalent voltage
5 W
, power consumption
*
No CE compliance above 60 Hz
Low Voltage/Power Option
20-36 Vdc,
4 W**
, power consumption
External power source must meet Safety
Agency Approvals.
**
Units can be powered safely with 24 Vac
but, no Certification for CE/UL are claimed.
External Fuse Required
Time-Delay, UL 248-14 listed:
100 mA/250 V
400 mA/250 V
(Low Voltage/Power Option)
Time-Lag, IEC 127-3 recognized:
100 mA/250 V
400 mA/250 V
(Low Voltage/Power Option)
Environmental Conditions
0 to 55°C (32 to 131°F),
90% RH non-condensing
0 to 50°C (32 to122°F) for UL only.
90% RH non-condensing
Protection
NEMA 1(Type 1) front bezel
1
⁄
8
DIN
NEMA 4 (IP65) front bezel
1
⁄
16
DIN
Dimensions
48 H x 96 W x 127 mm D
(1.89 x 3.78 x 5")
1
⁄
8
DIN
48 H x 48 W x 127 mm D
(1.89 x 1.89 x 5")
1
⁄
16
DIN
Panel Cutout
45 H x 92 W mm
(1.772" x 3.622 ")
1
⁄
8
DIN
45 mm (1.772") square
1
⁄
16
DIN
Weight
295 g (0.65 lb)
1
⁄
8
DIN
159 g (0.35 lb)
1
⁄
16
DIN
Summary of Contents for CNi16A
Page 62: ...4 1 1 8 DIN Mounting 58...
Page 63: ...4 2 1 16 DIN Mounting 59...
Page 69: ...NOTES...
Page 70: ...NOTES...
Page 71: ...NOTES...