14
PART 3
OPERATION: Configuration Mode
3.1 Introduction
The instrument has two different modes of operation. The first, Run Mode, is
used to display values for the Process Variable, and to display or clear Peak
and Valley values. The other mode, Menu Configuration Mode, is used to
navigate through the menu options and configure the controller. Part 3 of this
manual will explain the Menu Configuration Mode. For your instrument to
operate properly, the user must first "program" or configure the menu options.
Turning your Controller On for the First Time
The device becomes active as soon as it is connected to a power source. It
has no On or Off switch. The device at first momentarily shows the software
version number, followed by reset
RST
, and then proceeds to the Run Mode.
For first-time users: Refer to the QuickStart Manual for basic operation
and set-up instructions.
If you have the Serial Communications/Ethernet Option you can easily
configure the controller on your computer or on-line.
Table 3.1 Button Function in Configuration Mode
•
To enter the Menu, the user must first press
a
button.
• Use this button to advance/navigate to the next menu item. The user can navigate
through all the top level menus by pressing
a
.
• While a parameter is being modified, press
a
to escape without saving the parameter.
• Press the up
b
button to scroll through “flashing” selections. When a numerical value is
displayed press this key to increase value of a parameter that is currently being modified.
• Holding the
b
button down for approximately 3 seconds will speed up the rate at which
the set point value increments.
• In the Run Mode press
b
causes the display to flash the PEAK value – press again to
return to the Run Mode.
• Press the down
c
button to go back to a previous Top Level Menu item.
• Press this button twice to reset the controller to the Run Mode.
• When a numerical value is flashing (except set point value) press
c
to scroll digits from
left to right allowing the user to select the desired digit to modify.
• When a setpoint value is displayed press
c
to decrease value of a setpoint that is
currently being modified. Holding the
c
button down for approximately 3 seconds will
speed up the rate at which the setpoint value is decremented.
• In the Run Mode press
c
causes the display to flash the VALLEY value – press again to
return to the Run Mode.
• Press the enter
d
button to access the submenus from a Top Level Menu item.
• Press
d
to store a submenu selection or after entering a value — the display will flash a
STRD
message to confirm your selection.
• To reset flashing Peak or Valley press
d
.
• In the Run Mode, press
d
twice to enable Standby Mode with flashing
STBY
.
Reset:
Except for Alarms, modifying any settings of the menu configuration
will reset the instrument prior to resuming Run Mode.
a
MENU
b
(UP)
c
(DOWN)
d
ENTER