34
ALARM 2 ENABLE/DISABLE SUBMENU:
Press
d
5)
Display flashes previous selection. Press
b
until
ENBL
displays to use Alarm 2.
Press
d
6)
Display shows
STRD
stored message momentarily and then
advances to
ABSo
only if it was changed, otherwise press
a
to
advance to
ABSo
Absolute/Deviation Submenu.
If
DSBL
Alarm 2
Disabled
was selected, all submenus of Alarm
2 will be skipped and meter advances to
LOOP
Loop Break Time
Menu. If
ENBL
Alarm 2
Enabled
was selected, Output 2 will
automatically be
Disabled
, and reassigned as Alarm 2.
The remaining Alarm 2 menu items are identical to Alarm 1 Menu.
Modifying Alarm Settings will not reset the instrument.
3.2.10 Loop Break Time Menu
Figure 3.8 Flow Chart for Loop Break Time Menu
ENTER LOOP BREAK TIME MENU:
Press
a
1)
Press
a
, if necessary, until
CNFG
prompt appears.
Press
d
2)
Display advances to
INPT
Input Menu.
Press
a
3)
Press
a
, if necessary, until Display advances to
LOOP
Loop
Break Time Menu.
It
is required that you put the controller in the Standby Mode
for any configuration change other than Set Points & Alarms.
Summary of Contents for CNiS16
Page 69: ...NOTES 65...
Page 70: ...NOTES 66...