Disassembly Instruction:
If necessary, the unit may be removed from the panel and
opened.
Warning: Disconnect all ac power from the unit
before proceeding.
1.
Remove all wiring connections from the rear of the meter.
To remove connector assembly, squeeze top and
bottom of the case near the connector site for release,
then pull connectors from case.
2.
To remove meter from the case, squeeze top and bottom
of the bezel to release, then pull from case.
WIRING
Wire the instrument according to the figure shown below.
Warning: Do not connect ac power to your
device until you have completed all input and
output connections. This device must only be
installed by a specially trained electrician with
corresponding qualifications. Failure to follow all
instructions and warnings may result in injury!
This Quick Start Reference provides information
on setting up your instrument for basic operation.
The latest complete Communication and Operational
Manual as well as free Software and ActiveX Controls
are available at
www.omega.com/specs/iseries
or
on the CD-ROM enclosed with your shipment
.
SAFETYCONSIDERATION
This device is marked with the international
Caution symbol.
The instrument is a panel mount device protected in
accordance with EN61010-1:2001. Remember that the unit
has no power-on switch. Building installation should include
a switch or circuit-breaker that must be compliant to IEC
947-1 and 947-3.
SAFETY:
• Do not exceed voltage rating on the label located on
the top of the instrument housing.
• Always disconnect power before changing signal and
power connections.
• Do not use this instrument on a work bench without
its case for safety reasons.
• Do not operate this instrument in flammable or
explosive atmospheres.
• Do not expose this instrument to rain or moisture.
EMC:
• Whenever EMC is an issue, always use shielded cables.
• Never run signal and power wires in the same conduit.
• Use signal wire connections with twisted-pair cables.
• Install Ferrite Bead(s) on signal wire close to the
instrument if EMC problems persist.
MOUNTING
Panel Mounting Instruction:
1.
Using the dimensions from the panel cutout diagram
shown above, cut an opening in the panel.
2.
Insert the unit into the opening from the front of the panel,
so the gasket seals between the bezel and the front of the
panel.
3.
Slide the retainer over the rear of the case and tighten
against the backside of the mounting panel.
START HERE
Connect the main power connections in the figure shown below.
FUSE
Connector Output Type For 115Vac For 230Vac
DC
FUSE 1
Output 1
Relay
3 A(T)
3 A(T)
-
FUSE 2
Output 2
Relay
3 A(T)
3 A(T)
-
FUSE 3
Power
N/A
100 mA(T)
100 mA(T) 100 mA(T)
FUSE 4
Power
N/AN/AN/A
400 mA
(T)
CONFIGURATION
Button Functions in Configuration Mode
•
To enter the Menu, the user must first press
a
button.
•
Use this button to advance/navigate to the next
menu item. The user can navigate through all the
top level menus by pressing
a
.
•
While a parameter is being modified, press
a
to
escape without saving the parameter.
•
Press the up
b
button to scroll through “flashing”
selections. When a numerical value is displayed
press this key to increase value of a parameter
that is currently being modified.
•
Holding the
b
button down for approximately
3 seconds will speed up the rate at which the
setpoint value is incremented.
•
In the Run Mode pressing
b
causes the display to
flash the PEAK or GROSS value – press again to
return to the Run Mode.
•
Press the down
c
button to go back to a previous
Top Level Menu item.
•
Press this button twice to reset the controller to
the Run Mode.
•
When a numerical value is flashing (except
setpoint value) press
c
to scroll digits from left to
right allowing the user to select the desired digit to
modify.
•
When a setpoint value is displayed press
c
to
decrease value of a setpoint that is currently being
modified. Holding the
c
button down for
approximately 3 seconds will speed up the rate at
which the setpoint value is decremented.
•
In the Run Mode pressing
c
causes the display to
flash TARE value to tare your reading (zeroing).
•
Press the enter
d
button to access the submenus
from a Top Level Menu item.
•
Press
d
to store a submenu selection or after
entering a value — the display will flash a
STRD
message to confirm your selection.
•
To reset flashing PEAK or GROSS press
d
.
•
In the Run Mode, press
d
twice to enable
Standby Mode with flashing
STBY
.
1
2
3
4
5
6
7
8
Reset: Except for Alarms, modifying any settings of
the menu configuration will reset the controller prior
to resuming Run Mode.
DISPLAYABBREVIATIONS
SP1
Set Point 1 Value
SP2
Set Point 2 Value
CNFG
Configuration Menu
INPt
Input Type (Range)
INPt
Input Type (range)
0 - 0.1
100 mV Input
Voltage
0 - 1.0
1 V Input Voltage
0 - 10
10 V Input Voltage
0 - 20
20 mAInput Current
Rtio
Ratiometric Operation
RESO
Display Resolution
bUtN
Button Peak/Gross
PEAk
Peak Value
GROS
Gross Value
RdG
Reading Configuration
dEC
Decimal Point
F.FFF
Decimal Point
..FFFF
Position
LOAd
Input Load
EnbL
Scaling with Known
Loads (Actual Value)
DSbL
Scaling without Known
L.PNt
Linearization Points
Loads (Calculated Value)
0002..
Number of Linearization
FLtR
Filter Constant
..0010
Points
0001..
Filter Constant Value
IN.Rd
Input/Reading Scale
..0128
and Offset Menu
IN 1
Input 1
Rd 1
Reading 1
IN 2
Input 2
Rd 2
Reading 2
...
...
...
...
IN 10
Input 10
Rd 10
Reading 10
ANLG
Analog Output
CURR
Current Output
VoLt
Voltage Output
Rd 1
Reading 1
Out.1
Output 1
Rd 2
Reading 2
Out.2
Output 2
ALR1
Alarm 1 Menu
AbSo
Absolute Mode
_dEV
Deviation Mode
LtcH
Latched Mode
UNLt
Unlatched Mode
Ct.CL
Contact Closure
N.o.
Normally Open
N.c
.
Normally Closed
ActV
Active Type
AboV
Active Above
bELo
Active Below
Hi.Lo
Above High/Below
Low
bANd
Above or Below Band
A.P.oN
Alarm Enable/Disable
at Power On
ALR.L
Alarm Low Value
ALR.H
Alarm High Value
ALR.2
Alarm 2 Menu
LOOP
Loop Break Menu
b.tIM
Loop Break Time
R.AdJ
Reading Adjust
SP.dN
Set Point Deviation
OUt1
Output 1 Menu
SELF
Manual Control
ººLO
Percent Low
ººHI
Percent High
CtRL
Control Type
ON.OF
On/Off Control
4 -20
Amplitude Control
PId
PID Control
ActN
Action Type
RVRS
Reverse Action
dRct
Direct Action
ANt1
Anti Integral
AUto
Auto PID
A.tUN
Auto Tune PID
StRt
Start Auto Tune PID
PRoP
Proportional Band
RESt
Reset Setup
RAtE
Rate Setup
CYCL
Cycle Time
dPNG
Damping Factor
dEAd
Dead Band
OUt2
Output 2 Menu
RAMP
Ramp Time
SOAk
Soak Time
Id
ID Code Menu
CH.Id
Change ID Code
FULL
Full ID
SP.Id
Set Point ID
COMM
Communication Option*
NONE
Communication is
Not Installed
COLR
Display Color Selection
N.CLR
Normal Color Display
1.CLR
Alarm 1 Color Display
2.CLR
Alarm 2 Color
Display
REd
Display Color is Red
AMbR
Display Color is
Amber
GRN
Display Color is Green
dSbL
Disable
ENbL
Enable
ERRO
Error
+ OL
Input (+) Overload
* For abbreviations of Communication Option see Communication Manual.
a
d
c
b
PK/GRS
(UP)
MENU
TARE
(DOWN)
ENTER
If instrument has the
communication option,
the internal excitation
is not available. Use
external excitation to
power your transducer.
See Specification Section
2
1
2
1