background image

Disassembly Instruction:

If necessary, the unit may be removed from the panel and
opened.

Warning: Disconnect all ac power from the unit
before proceeding.

1.

Remove all wiring connections from the rear of the meter.
To remove connector assembly, squeeze top and
bottom of the case near the connector site for release,
then pull connectors from case. 

2.

To remove meter from the case, squeeze top and bottom
of the bezel to release, then pull from case.

WIRING

Wire the instrument according to the figure shown below.

Warning: Do not connect ac power to your
device until you have completed all input and
output connections. This device must only be
installed by a specially trained electrician with
corresponding qualifications. Failure to follow all
instructions and warnings may result in injury!

This Quick Start Reference provides information 
on setting up your instrument for basic operation. 
The latest complete Communication and Operational
Manual as well as free Software and ActiveX Controls
are available at  

www.omega.com/specs/iseries

or 

on the CD-ROM enclosed with your shipment

.

SAFETYCONSIDERATION

This device is marked with the international
Caution symbol.

The instrument is a panel mount device protected in
accordance with EN61010-1:2001. Remember that the unit
has no power-on switch. Building installation should include
a switch or circuit-breaker that must be compliant to IEC
947-1 and 947-3.

SAFETY:

• Do not exceed voltage rating on the label located on 

the top of the instrument housing.

• Always disconnect power before changing signal and 

power connections.

• Do not use this instrument on a work bench without 

its case for safety reasons.

• Do not operate this instrument in flammable or 

explosive atmospheres.

• Do not expose this instrument to rain or moisture.

EMC:

• Whenever EMC is an issue, always use shielded cables. 
• Never run signal and power wires in the same conduit.
• Use signal wire connections with twisted-pair cables.
• Install Ferrite Bead(s) on signal wire close to the 

instrument if EMC problems persist. 

MOUNTING

Panel Mounting Instruction:
1.

Using the dimensions from the panel cutout diagram 
shown above, cut an opening in the panel.

2.

Insert the unit into the opening from the front of the panel, 
so the gasket seals between the bezel and the front of the 
panel.

3.

Slide the retainer over the rear of the case and tighten 
against the backside of the mounting panel.

START HERE

Connect the main power connections in the figure shown below.

FUSE

Connector Output Type For 115Vac  For 230Vac

DC

FUSE 1

Output 1

Relay

3 A(T)

3 A(T)

FUSE 2

Output 2 

Relay 

3 A(T) 

3 A(T) 

-

FUSE 3

Power 

N/A

100 mA(T) 

100 mA(T)  100 mA(T)

FUSE 4

Power

N/AN/AN/A

400 mA

(T)

CONFIGURATION

Button Functions in Configuration Mode

To enter the Menu, the user must first press 

a

button.

Use this button to advance/navigate to the next
menu item. The user can navigate through all the
top level menus by pressing 

a

.

While a parameter  is being modified, press 

a

to

escape without saving the parameter.

Press the up 

b

button to scroll through “flashing”

selections. When a numerical value is displayed
press this key to increase value of a parameter
that is currently being modified.

Holding the 

b

button down for approximately 

3 seconds will speed up the rate at which the
setpoint value is incremented.  

In the Run Mode pressing 

b

causes the display to

flash the PEAK or GROSS value – press again to
return to the Run Mode.

Press the down 

c

button to go back to a previous

Top Level Menu item. 

Press this button twice to reset the controller to
the Run Mode. 

When a numerical value is flashing (except
setpoint value) press 

c

to scroll digits from left to

right allowing the user to select the desired digit to
modify.

When a setpoint value is displayed press 

c

to

decrease value of a setpoint that is currently being
modified. Holding the 

c

button down for

approximately 3 seconds will speed up the rate at
which the setpoint value is decremented.

In the Run Mode pressing 

c

causes the display to

flash TARE value to tare your reading (zeroing).

Press the enter 

d

button to access the submenus

from a Top Level Menu item. 

Press 

d

to store a submenu selection or after

entering a value — the display will flash a 

STRD

message to confirm your selection.

To reset flashing PEAK or GROSS press 

d

.

In the Run Mode, press 

d

twice to enable

Standby Mode with flashing 

STBY

.

1

2

3

4

5

6

7

8

Reset: Except for Alarms, modifying any settings of
the menu configuration will reset the controller prior
to resuming Run Mode.

DISPLAYABBREVIATIONS

SP1

Set Point 1 Value

SP2

Set Point 2 Value

CNFG

Configuration Menu

INPt

Input Type (Range)

INPt

Input Type (range)

0 - 0.1

100 mV Input
Voltage

0 - 1.0

1 V Input Voltage

0 - 10

10 V Input Voltage

0 - 20

20 mAInput Current

Rtio

Ratiometric Operation

RESO

Display Resolution

bUtN

Button Peak/Gross

PEAk

Peak Value

GROS

Gross Value

RdG

Reading Configuration

dEC

Decimal Point

F.FFF

Decimal Point

..FFFF

Position

LOAd

Input Load

EnbL

Scaling with Known
Loads (Actual Value)

DSbL

Scaling without Known

L.PNt

Linearization Points

Loads (Calculated Value)

0002..

Number of Linearization

FLtR

Filter Constant

..0010

Points

0001..

Filter Constant Value

IN.Rd

Input/Reading Scale

..0128

and Offset Menu

IN 1

Input 1

Rd 1

Reading 1

IN 2

Input 2

Rd 2

Reading 2

...

...

...

...

IN 10

Input 10

Rd 10

Reading 10

ANLG

Analog Output

CURR

Current Output

VoLt

Voltage Output

Rd 1

Reading 1

Out.1

Output 1

Rd 2

Reading 2

Out.2

Output 2

ALR1

Alarm 1 Menu

AbSo

Absolute Mode

_dEV

Deviation Mode

LtcH

Latched Mode

UNLt

Unlatched Mode

Ct.CL

Contact Closure 

N.o.

Normally Open

N.c

.

Normally Closed

ActV

Active Type

AboV

Active Above

bELo

Active Below

Hi.Lo

Above High/Below
Low 

bANd

Above or Below Band

A.P.oN

Alarm Enable/Disable
at Power On

ALR.L

Alarm Low Value

ALR.H

Alarm High Value

ALR.2

Alarm 2 Menu

LOOP

Loop Break Menu

b.tIM

Loop Break Time

R.AdJ

Reading Adjust

SP.dN

Set Point Deviation

OUt1

Output 1 Menu

SELF

Manual Control

ººLO

Percent Low 

ººHI

Percent High

CtRL

Control Type

ON.OF

On/Off Control

4 -20

Amplitude Control

PId

PID Control

ActN

Action Type

RVRS

Reverse Action

dRct

Direct Action

ANt1

Anti Integral

AUto

Auto PID 

A.tUN

Auto Tune PID

StRt

Start Auto Tune PID

PRoP

Proportional Band

RESt

Reset Setup 

RAtE

Rate Setup

CYCL

Cycle Time 

dPNG

Damping Factor

dEAd

Dead Band

OUt2

Output 2 Menu

RAMP

Ramp Time

SOAk

Soak Time

Id

ID Code Menu

CH.Id

Change ID Code

FULL

Full ID

SP.Id

Set Point ID

COMM

Communication Option*

NONE

Communication is
Not Installed

COLR

Display Color Selection

N.CLR

Normal Color Display

1.CLR

Alarm 1 Color Display

2.CLR

Alarm 2 Color
Display

REd

Display Color is Red

AMbR

Display Color is
Amber

GRN

Display Color is Green

dSbL

Disable

ENbL

Enable

ERRO

Error

+ OL

Input (+) Overload

* For abbreviations of Communication Option see Communication Manual.

a

d

c

b

PK/GRS

(UP) 

MENU

TARE

(DOWN)

ENTER

If instrument has the
communication option,
the internal excitation
is not available. Use
external excitation to
power your transducer.

See Specification Section

2

1

2

1

Reviews: