Getting Started with the Model DMD-476

1. Excitation Supply. If remote sensing is not used, cSense to +Excitation, terminal 3 to 4, and

connect -Sense to -Excitation, terminal 1 to 2.

2. Apply power to the DMD-476 and adjust the Excitation supply. Turn SWB-1 “ON” for a fixed 10 Volts.

This will set the supply to 10.2 ±2.5% and provide the best temperature stability. For voltages between
5 and 10 Volts, place SWB-1 in the “OFF” position and set the Excitation Supply with potentiometer
E. SWB-2 may be in either position.

3. Turn the power to the DMD-476 off and connect the load cell to the DMD-476 Excitation terminals and

the Amplifier Inputs.

4. Turn on power to the DMD-476.

5. Turn SWA-3 “ON”. (To set output ZERO current with pot D.)

6. Select the expected full scale signal range according to the table with SWA-4 and

SWA-5. If the output from the load cell is not known, set both SW-4 and
SW-5 “ON” for the 40-50mV range.

7. Set SWA-2 “OFF” for 4mA or SWA-2 “ON” for 0mA output ZERO.

8. Adjust D potentiometer for desired ZERO current.

9. Turn SWA-3 “OFF”. Expect output current to change.

10. Apply no load or dead weight to load cell.

11. Adjust TARE potentiometers A and B for the same ZERO current set in Step 8.

SWA-1 “OFF” provides a bridge output balance of -3mV to +15mV, and “ON” b15mV and
+25mV.

12. Apply full scale load and adjust SPAN (GAIN) potentiometer C for the desired full scale output current.

Set Range switches SWA-4 and SWA-5 as required.

13. Remove full scale load and check ZERO output current. Adjust FINE TARE potentiometer A if required.

14. Recheck full scale as in Step 12.

15. End.

Note: If the amplifier is used without using the DMD-476 Excitation Supply, the external power supply low

side must be connected to the -EXCITATION terminal 2 on the Model DMD-476, or one of the inputs
must be tied to terminal 2, -EXCITATION. This provides a DC return path for the finite amplifier input
current.

Summary of Contents for DMD-476

Page 1: ... An OMEGA Technologies Company User s Guide http www omega com e mail info omega com DMD 476 Bridgesensor AC Powered Signal Conditioner ...

Page 2: ...0 4 06342 e mail france omega com Germany Austria Germany Austria Germany Austria Germany Austria Germany Austria Daimlerstrasse 26 D 75392 Deckenpfronn Germany Tel 49 07056 3017 FAX 49 07056 8540 Toll Free in Germany 0130 11 21 66 e mail info omega de United Kingdom United Kingdom United Kingdom United Kingdom United Kingdom One Omega Drive River Bend Technology Centre ISO 9002 Certified Northban...

Page 3: ... i r B V m 5 2 o t V m 3 f o S F 0 8 s l a u q E l l e c V V m 3 e c n a t s i s e R t u p n I e d o M n o m m o C d n a l a i t n e r e f f i D m h o g e m 0 0 0 1 C D n o i t c e j e R e d o M n o m m o C m u m i n i m B d 0 0 1 t u p n I e d o M n o m m o C s t l o V 5 t u p t u O t s u j d A o r e Z A m 4 r o 0 t n e i c i f f e o C e r u t a r e p m e T 1m C A n a p S t u p t u O t n e r r u ...

Page 4: ...0 5 o t V m 0 4 F F O N O V m 0 4 o t V m 0 2 N O F F O V m 0 2 o t V m 0 1 F F O F F O V m 0 1 o t V m 5 1 B W S e g a t l o V n o i t a t i c x E N O s t l o V 0 1 d e x i F F F O e l b a t s u j d A s t n e m n g i s s A p i r t S l a n i m r e T w e r c S l a n i m r e T n o i t c n u F w e r c S l a n i m r e T n o i t c n u F 1 E S N E S 6 C A 2 N O I T A T I C X E 7 L A N G I S 3 E S N E S ...

Page 5: ...oad cell is not known set both SW 4 and SW 5 ON for the 40 50mV range 7 Set SWA 2 OFF for 4mA or SWA 2 ON for 0mA output ZERO 8 Adjust D potentiometer for desired ZERO current 9 Turn SWA 3 OFF Expect output current to change 10 Apply no load or dead weight to load cell 11 Adjust TARE potentiometers A and B for the same ZERO current set in Step 8 SWA 1 OFF provides a bridge output balance of 3mV to...

Page 6: ...rnal supply must be connected to the DMD 476 common Terminal 2 Be sure that the common mode voltage limits are observed This would generally limit the external power supply to 10 Volts assuming that half the voltage would be common mode as is the case when exciting a full bridge When the full scale output of a sensor is measured in millivolts say 10 millivolts care must be exercised in wiring syst...

Page 7: ...ise shall not exceed the purchase price of the component upon which liability is based In no event shall OMEGA be liable for consequential incidental or special damages CONDITIONS Equipment sold by OMEGA is not intended to be used nor shall it be used 1 as a Basic Component under 10 CFR 21 NRC used in or with any nuclear installation or activity or 2 in medical applications or used on humans Shoul...

Page 8: ...wheel Systems þ Totalizers Batch Controllers pH CONDUCTIVITY þ pH Electrodes Testers Accessories þ Benchtop Laboratory Meters þ Controllers Calibrators Simulators Pumps þ Industrial pH Conductivity Equipment DATA ACQUISITION þ Data Acquisition Engineering Software þ Communications Based Acquisition Systems þ Plug in Cards for Apple IBM Compatibles þ Datalogging Systems þ Recorders Printers Plotter...

Reviews: