31
Configuring The Meter
4
4.6 USING SETPOINT 1 CONFIGURATION
S1.CF
Refer to Table 6-1 for a summary list of menu configuration.
Setpoint 1 Configuration
S1.CF
is not active unless your meter has dual relay output
capabilities. The LED's will display whether the
S1.CF
is active or not. You may use
Setpoint 1 Configuration
S1.CF
for the following:
•
To set the setpoint's active band above or below your chosen value
•
To select whether the setpoint operation is latched or unlatched
4.6.1 Setting Setpoint 1's Active Band
1.
Press the
MENU
button until the meter shows
S1.CF
.
2.
Press the
∂
TARE
button. The meter shows one of the following:
•
S.1=A
(Active above the setpoint)
(Default)
•
S.1=B
(Active below the setpoint)
3.
Press the
ß
MAX
button to toggle between available choices.
4.
Press the
∂
TARE
button to select if Setpoint 1 is latched or unlatched or press the
MENU
button to store your selection.
4.6.2 Selecting if Setpoint 1 is Latched or Unlatched
1.
Press the
MENU
button until
S1.CF
displays, then press the
∂
TARE
button twice.
or
Press the
∂
TARE
button from
S.1
.
The meter shows one of the following:
•
S.2=U
Setpoint 1 to be unlatched
(Default)
•
S.2=L
Setpoint 1 to be latched
2.
Press the
ß
MAX
button to toggle between available choices.
3.
Press the
MENU
button to store your selection(s). The meter momentarily shows
STRD
, followed by
S2.CF
(Setpoint 2 Configuration).