48
FC-21 Flow Computer
8.2.8
Calibrate CH2 0mA
Submenu Group
8.2.9
Calibrate CH2 20mA
Submenu Group
Calibrate ch2 0mA
Iin=TB1-8 GND=TB1-4
Calibrate ch2 0mA
0 CALIBRATING ——
Calibrate ch2 0mA
*** DONE ***
Calibrate ch2 0mA
Iin=TB1-8 GND=TB1-4
Calibrate ch2 20mA
Iin=TB1-8 GND=TB1-4
Calibrate ch2 20mA
0 CALIBRATING ——
Calibrate ch2 20mA
*** DONE ***
Calibrate ch2 20mA
Iin=TB1-8 GND=TB1-4
Advance to
Calibrate ch1 0V
To Calibrate: Connect Current Source (+)
TB1-8, (-) TB1-4. Input 0mA and press Enter.
This message is displayed during calibration.
This message is displayed when the 0mA
calibration is finished.
The display will automatically return to the
Calibrate CH2 0mA submenu. Press the
Down arrow key to advance to the CH2 20mA
calibration.
To Calibrate: Connect Current Source (+)
TB1-8, (-) TB1-4. Input 20mA and press
Enter.
This message is displayed during calibration.
This message is displayed when the 20mA
calibration is finished.
The display will automatically return to the
Calibrate CH2 20mA submenu. Press the
Down arrow key to advance to the CH1 0V
calibration.
ENTER
STOP
ENTER
STOP
Sub-menus
Display
Notes