10
PROGRAMMING SETUP-LEVEL
GENERAL
Configuration of the FPD3100-D-A is done at SETUP-level. SETUP-level is
reached by pressing the PROG/ENTER key for 7 seconds; at which time, setup
will be displayed. In order to return to the operator level, PROG will have to be
pressed for three seconds. Alternatively, if no keys are pressed for 2 minutes,
the unit will exit SETUP automatically.
SETUP can be reached at all times while the register remains fully operational.
FPD3100-D-A DIGITAL REGISTER
Program Overview
SETUP FUNCTIONS AND VARIABLES DRA
OPERATE / RUN TIME VARIABLES
TOTAL / BATCH TOTAL
DEFAULT
11
UNIT
L, m3, US-GAL, UK-GAL, US-bbl, UK-bbl, OIL-bbl.
L
12
DECIMALS
0 - 1 - 2 – 3
0
ACCUMULATED TOTAL
DEFAULT
21
UNIT
L, m3, US-GAL, UK-GAL, US-bbl, UK-bbl, OIL-bbl.
L
22
DECIMALS
0 - 1 - 2 – 3
0
FLOWRATE
DEFAULT
31
UNIT
L, m3, US-GAL, UK-GAL, US-bbl, UK-bbl, OIL-bbl.
L
32
TIME UNIT
sec - min - hour
min
33
DECIMALS
0 - 1 - 2 – 3
0
34
CALCULATION
per 1 – 255 pulses
10
35
CUT-OFF
0.1 – 999.9 seconds
30.0
ALARM
DEFAULT
41
FLOW ALARM
operate - hidden - off
off
42
FLOW ZERO
on - off
on
43
ALARM LOW
0000.000 unit/time unit
0
44
ALARM HIGH
0000.000 unit/time unit
99999
45
DELAY ALARM
0… 99 seconds
0
FLOWMETER
DEFAULT
51
K-FACTOR
0000.001 - 9999.999 pulses / unit of measure
1.000
ANALOG OUTPUT
DEFAULT
61
LOW FLOW
0000.000 - 9,999,999 unit/time unit
0
62
HIGH FLOW
0000.000 - 9,999,999 unit/time unit
99999
63
LOW CALIB - 4mA
0 - 9999
631
64
HIGH CALIB - 20mA
0 - 9999
3200
PULSE OUTPUT
DEFAULT
71
DECIMALS
0 - 1 - 2 – 3
0
72
PULSE WIDTH
0.005 - 1.000 sec
0
73
PULSE PER
X,XXX,XXX quantity
1000
OTHERS
DEFAULT
81
MODEL / TYPE
DRA
-
82
SOFTWARE VERSION
xx.xx.xx
-
83
SERIAL NO.
xxxxxxx
-