MCAC-KTSM-2009-03
Specifications
Heat Recovery Ventilation
5
Sale Model
HRV-500
HRV-800
HRV-1000
Code 220082100210
220082100220
220082100230
Power supply
V-Ph-Hz
220V-1Ph-50Hz
220V-1Ph-50Hz
220V-1Ph-50Hz
Temp. efficiency
%
60
60
60
Cooling
Enthalpy efficiency
%
50
50
50
Temp. efficiency
%
70
70
70
Heating
Enthalpy efficiency
%
60
60
60
Model
YDK60-4D01
YDK-180-4P01
YDK-10-4(992A1)
Insulation class
B
B
B
Safe class
IP34
IP34
IP34
Input W
120
360
360
Rated current
A
1
2
2.4
Capacitor uF
3.5
8
7
Indoor fan motor
Speed r/min
1250
1350
1150
material
ABS
ABS
ABS
Type
Centrifugal fan
Centrifugal fan
Centrifugal fan
Diameter mm
Φ
205
Φ
246
Φ
246
Indoor fan
Height mm
140
203
203
Indoor air flow
m
3
/h 500
800
1000
Indoor external static pressure (Hi)
Pa
80
100
100
Indoor sound level (sound pressure level)
dB(A)
35
39
40
Dimension (W×H×D)
mm
824×270×904
1116×388×884
1116×388×1134
Packing (W×H×D)
mm
1126×462×1159
1418×580×1139
1418×580×1389
Indoor unit
Net/Gross weight
kg
35.5/65.5 57.5/91.5
59/95
Power wiring
mm
2
3×2.5
3×2.5
3×2.5
Connection wiring
Signal wiring
mm
2
3×0.75
3×0.75
3×0.75
Controller
Wired
controller (KJR-27B/E)
Fresh Air Diameter
mm
Φ
194
Φ
242
Φ
242
Fresh air
Air drop (static pressure)
Pa
80
100
150
Summary of Contents for HRV-200