Input Type (Process)
ENTER INPUT TYPE MENU:
Press
a
1)
Press
a
, if necessary, until
CNFG
prompt appears.
Press
d
2)
Display advance to
INPT
Input Menu.
Press
d
3)
Display flashes
T.ç
,
RTD
or
PROC
(Thermocouple, RTD or
Process). If the displayed input type is
PROC
, press
a
to skip to
step 6 (
PROC
stops flashing).
PROCESS SUBMENU:
Press
b
4)
Scroll through the available selection to
PROC
(flashing).
Press
d
5)
Display shows
STRD
stored message momentarily and then
PROC
(not flashing).
Press
d
6)
Display flashes previous Process type selection. i.e.
0-10
(see below for Process types selection).
Press
b
7)
Scroll through the available Process types to the selection of
your choice.
Press
d
8)
Display shows
STRD
stored message and then advances to
RDG
Reading Configuration Menu.
Process Types:
100 mV 1 V
10 V
0 – 20 mA
Display:
0-0.1
0-1.0
0-10
0-20
For 4-20 mA Input select 0-20 mA then adjust the Input/Reading accordingly.
To adjust 4-20 mA input, see example under INPUT/READING Submenu. The
factory preset value is 4-20 mA.
19