28
3.2.8 Alarm 1 Menu
Figure 3.8 Flow Chart for Alarm 1 Menu
ENTER ALARM 1 MENU:
Press
a
1)
Press
a
, if necessary, until
CNFG
prompt appears.
Press
d
2)
Display advances to
INPT
Input Menu.
Press
a
3)
Press
a
, if necessary, until display advances to
ALR1
Alarm 1
Menu.
Press
d
4)
Display advances to
LTCH
Latch.
ALARM 1 LATCH SUBMENU:
Press
d
5)
Display flashes previous selection. Press
b
to
ENBL
Enable
or
DSBL
Disable.
Press
d
6)
Display shows
STRD
stored message momentarily and then
advances to
AçTV
only, if it was changed, otherwise press
a
to
advance to
AçTV
Active Submenu.
Latch Enabled:
Alarm remains "latched" until reset. To reset already latched
alarm, select Alarm Latch Enable and press Max twice (i.e. Disable and then go
back to Latch) or from a Run Mode, push
d
twice to put the monitor in Standby
Mode and then push
d
one more time to return to the Run Mode.
Latch Disabled:
Alarm remains latched only as long as the alarm condition is true.
ACTIVE SUBMENU:
Press
d
7)
Display flashes previous selection. Press
b
to
ABoV
Above,
or
BELo
Below.
Press
d
8)
Display shows
STRD
stored message momentarily and then
advances to
DEAD
Deadband.
DEADBAND SUBMENU:
Press
d
9)
Display shows
020.0
Deadband value that can be changed
by pressing
b
or
c
.
Press
d
10)
Display shows
STRD
stored message momentarily and then
advances to
ALR2
Alarm 2.