PART 1
INTRODUCTION
1.1 Description
This meter with simplified menu is an ON/OFF controller. It can also be
purchased as monitor (read process value only), limit alarm meter or as a
PID controller.
•
The iSeries offers unparalleled flexibility in process measurement. Each unit
allows the user to select the input type, from 10 thermocouple types (J, K, T,
E, R, S, B, C, N and J DIN), Pt RTDs (100, 500 or 1000 Ω, with either 385 or
392 curve), DC voltage, or DC current. The voltage/current inputs are fully
scalable to virtually all engineering units, with selectable decimal point,
perfect for use with pressure, flow or other process input.
•
The iSeries device features a large, three color programmable display with
capability to change a color every time the Alarm is triggered. The standard
features include built-in 24 Vdc @ 25 mA excitation for transmitters or other
devices. (Built-in excitation is not available with optional isolated RS-232/485
Serial Communication). Universal power supply accepts 90 to 240 Vac. Low
voltage power option accepts 24 Vac or 12 to 36 Vdc.
2