Page 28
iDRX-RTD SPECIFICATIONS
SPECIFICATIONS:
100, 500, 1000 Ohm platinum RTD with both European
(alpha=0.00385) and American (alpha=0.00392) curves.
Input Type:
100 Ohm
-328 to 1562 °F -200 to 850 °C
500 Ohm
-328 to 1562 °F -200 to 850 °C
1000 Ohm
-328 to 1562 °F -200 to 850 °C
ISOLATION:
Dielectric strength per 1 minute test based on
EN 61010 for 50 Vdc or Vrms working voltage.
Three way Isolation:
• Power to input 1800V Peak
• Power to analog output/communication 1800V Peak
• Input to analog output/communication 1400V Peak
INPUT OVER-VOLTAGE PROTECTION:
250 V AC for 1 Minute
ANALOG TO DIGITAL TECHNIQUE:
Dual slope
READ RATE:
3 readings/second, automatic polarity
ACCURACY AT 25 °C:
±0.5 °C for platinum RTD’s
TEMPERATURE STABILITY:
0.05 °C/°C
STEP RESPONSE FOR RS485 OUTPUT:
2 seconds to 99% of the final value
(Filter time constant = 64)
RESPONSE TIME:
To verify the response time, check the carriage return <CR>,
it will be sent at the end of the response. You can send
another command after you receive the <CR>.
i.e.
send: *01X01
response: 01X01<DATA><CR>
Note: 01 is address.
WARM UP TO RATED ACCURACY:
30 minutes
INPUT POWER:
10 to 32 Vdc
POWER CONSUMPTION:
2.4 Watts (100 mA at 24 Vdc)
OPERATING AMBIENT:
-5 to +55 °C
STORAGE TEMPERATURE:
-40 to +85 °C
RELATIVE HUMIDITY:
90% at 40 °C non-condensing
J 4
J 1
J 2
J 3
2 W I R E
+ E X C
- E X C
- S I G
+ S I G
+ E X C
- E X C
- S I G
+ S I G
J 2
+ E X C
- E X C
- S I G
+ S I G
R T D
R T D
4 W I R E
3 W I R E
J 2