60
EXCITATION
(optional in place of
Communication)
24 Vdc @ 25 mA
INSULATION
Power to Input/Output
2500 Vac per 1 minute test
(RS-232/485, Input or Output)
Between Inputs
500 Vac per 1 minute test
Approvals
See CE Approval Section
GENERAL
Power
100-240 Vac +/-10%, 50/60 Hz
22.5 W
Fuse
4A, 250V, GFE, 5x20mm
Environmental Conditions
0 to 40°C (32 to 104°F),
90% RH non-condensing
Installation Category
II per EN61010-1
Equipment Class
I per EN61010-1
Pollution Degree
2 per EN61010-1
Protection
NEMA-4x (IP65) front bezel
Dimensions and Panel Cutout
Refer to Quickstart Specifications.
Weight
Refer to Quickstart Specifications.
CONTROL OUTPUT 1 & 2
Relay
250 Vac or 30 Vdc @ 3 A
(Resistive Load); configurable for
on/off, PID and Ramp and Soak
Output 1:
SPDT type, can be
configured as Alarm 1 output
Output 2:
SPDT type, can be
configured as Alarm 2 output
SSR
20-265 Vac @ 0.05-0.5 A
(Resistive Load); continuous
DC Pulse
Non-Isolated; 10 Vdc @ 20 mA
Analog Output
(Output 1 only)
Non-Isolated, Proportional 0 to 10 Vdc
or 0 to 20 mA; 500 Ω max
COMMUNICATIONS (optional)
RS-232 or RS-485 programmable
300 to 19.2 K baud; complete
programmable setup capability;
program to transmit current display,
alarm status, Peak and Valley value.
RS-485
Addressable from 0 to 199
Connection
Screw terminals
ALARM 1 & 2 (programmable):
Type
Same as Output 1 & 2
Operation
High/low, above/below, band,
latch/unlatch, normally open/normally
closed and process/deviation; front
panel configurations
ANALOG OUTPUT (programmable)
Non-Isolated, Retransmission 0 to 10
Vdc or 0 to 20 mA, 500 Ω max (Output
1 only). Accuracy is + 1% of FS when
following conditions are satisfied.
1) Input is not scaled below 1% of
Input FS.
2) Analog Output is not scaled below
3% of Output FS.