background image

WARRANTY/DISCLAIMER

OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of

one (1) year

from the date of purchase. In addition to OMEGA’s standard warranty period, OMEGA Engineering will

extend  the  warranty  period  for 

four  (4)  additional  years

if  the  warranty  card  enclosed  with  each  instrument  is

returned to OMEGA.

If  the  unit  should  malfunction,  it  must  be  returned  to  the  factory  for  evaluation.  OMEGA’s  Customer  Service
Department  will  issue  an Authorized  Return  (AR)  number  immediately  upon  phone  or  written  request.  Upon
examination by OMEGA, if the unit is found to be defective, it will be repaired or replaced at no charge. OMEGA’s
WARRANTY does  not  apply  to  defects  resulting  from  any  action  of  the  purchaser,  including  but  not  limited  to
mishandling, improper interfacing, operation outside of design limits, improper repair, or unauthorized modification.
This WARRANTY is VOID if the unit shows evidence of having been tampered with or shows evidence of having
been  damaged  as  a  result  of  excessive  corrosion;  or  current,  heat,  moisture  or  vibration;  improper  specification;
misapplication; misuse or other operating conditions outside of OMEGA’s control. Components which wear are not
warranted, including but not limited to contact points, fuses, and triacs.

OMEGA is  pleased  to  offer  suggestions  on  the  use  of  its  various  products.  However,  OMEGA neither
assumes responsibility for any omissions or errors nor assumes liability for any damages that result from
the  use  of  its  products  in  accordance  with  information  provided  by  OMEGA,  either  verbal  or  written.
OMEGA warrants only that the parts manufactured by it will be as specified and free of defects. OMEGA
MAKES  NO  OTHER  WARRANTIES  OR  REPRESENTATIONS  OF  ANY KIND  WHATSOEVER,  EXPRESS  OR
IMPLIED,  EXCEPT  THAT  OF  TITLE,  AND  ALL IMPLIED  WARRANTIES  INCLUDING  ANY WARRANTY OF
MERCHANTABILITY AND  FITNESS  FOR  A PARTICULAR  PURPOSE  ARE  HEREBY DISCLAIMED.
LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability
of  OMEGA with  respect  to  this  order,  whether  based  on  contract,  warranty,  negligence,  indemnification,
strict  liability  or  otherwise,  shall  not  exceed  the  purchase  price  of  the  component  upon  which  liability  is
based. In no event shall OMEGA be liable for consequential, incidental or special damages.

CONDITIONS:  Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic
Component”  under  10  CFR  21  (NRC),  used  in  or  with  any  nuclear  installation  or  activity;  or  (2)  in  medical
applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity,
medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as set forth
in  our  basic  WARRANTY / DISCLAIMER  language,  and,  additionally,  purchaser  will  indemnify  OMEGA and
hold  OMEGA harmless  from  any  liability  or  damage  whatsoever  arising  out  of  the  use  of  the  Product(s)  in
such a manner.

RETURN REQUESTS/INQUIRIES

Direct  all  warranty  and  repair  requests/inquiries  to  the  OMEGA Customer  Service  Department.  BEFORE
RETURNING ANY PRODUCT(S)  TO  OMEGA,  PURCHASER  MUST OBTAIN AN AUTHORIZED  RETURN
(AR)  NUMBER  FROM  OMEGA’S  CUSTOMER  SERVICE  DEPARTMENT (IN  ORDER  TO AVOID
PROCESSING  DELAYS).  The  assigned AR  number  should  then  be  marked  on  the  outside  of  the  return
package and on any correspondence.
The  purchaser  is  responsible  for  shipping  charges,  freight,  insurance  and  proper  packaging  to  prevent
breakage in transit.  

FOR WARRANTY RETURNS, please have the 
following information available BEFORE 
contacting OMEGA:
1. Purchase Order number under which the product 

was PURCHASED,

2. Model and serial number of the product under

warranty, and

3. Repair instructions and/or specific problems 

relative to the product.

FOR NON-WARRANTY REPAIRS, consult OMEGA for
current repair charges. Have the following information
available BEFORE contacting OMEGA:
1.  Purchase Order number to cover the COST

of the repair,

2. Model and serial number of product, and
3. Repair instructions and/or specific problems 

relative to the product.

OMEGA’s  policy  is  to  make  running  changes,  not  model  changes,  whenever  an  improvement  is  possible.  This  affords  our
customers the latest in technology and engineering.

© Copyright 2004 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied, reproduced,
translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the prior written consent of
OMEGA ENGINEERING, INC.

TRADEMARK NOTICE: 

®

,

omega.com

®

,

, and  ™ are Trademarks of OMEGA ENGINEERING, INC.

PATENT  NOTICE: 

This  product  is  covered  by  one  or  more  of  the  following  patents:  U.S.  Pat.  No.  Des.  336,895;  5,274,577;

6,243,021 / CANADA 2052599; 2052600 / ITALY 1249456; 1250938 / FRANCE BREVET No. 91 12756 / SPAIN 2039150; 2048066 /
UK PATENT No. GB2 249 837; GB2 248 954 / GERMANY DE 41 34398 C2. Other US and International Patents pending or applied
for.

®

Summary of Contents for ILD24-UTP

Page 1: ...iLD24 UTP iLD44 UTP Big Display UniversalTemperature Process Controller Manual User sGuide www omega com e mail info omega com iSeries info www omega com specs iSeries Shop on line at ...

Page 2: ... e mail info omega ca For immediate technical or application assistance USA and Canada Sales Service 1 800 826 6342 1 800 TC OMEGA Customer Service 1 800 622 2378 1 800 622 BEST Engineering Service 1 800 872 9436 1 800 USA WHEN Mexico and TEL 001 800 TC OMEGA FAX 001 203 359 7807 Latin America En Español 001 203 359 7803 e mail espanol omega com Servicing Europe Benelux Postbus 8034 1180 LA Amstel...

Page 3: ...r Instrument On for the First Time Buttons Functions in Configuration Mode 3 2 Menu Configuration 15 3 2 1 ID Number 16 3 2 2 Setpoints 17 3 2 3 Configuration Menu 18 3 2 4 Input Type Menu 18 Input Type Thermocouple 19 Input Type RTD 20 Input Type Process 21 3 2 5 Reading Configuration Menu 21 3 2 6 Alarm 1 Menu 25 3 2 7 Analog Output Retransmission Menu 29 3 2 8 Alarm 2 Menu 32 3 2 9 Loop Break T...

Page 4: ...2 Excitation Output 13 Figure 2 13 Snubber Circuits Wiring Hookup 13 Figure 3 1 Flow Chart for ID and Setpoints 15 Figure 3 2 Flow Chart for Configuration Menu 18 Figure 3 3 Flow Chart for Input Type Menu 18 Figure 3 4 Flow Chart for Reading Configuration 21 Figure 3 5 Flow Chart for Alarm 1 25 Figure 3 6 Flow Chart for Analog Output Retransmission 29 Figure 3 7 Flow Chart for Alarm 2 32 Figure 3 ...

Page 5: ...vides you with information that is important to successfully setup and use the Programmable Digital Meter CAUTION or WARNING Tells you about the risk of electrical shock CAUTION WARNING or IMPORTANT Tells you of circumstances or practices that can effect the instrument s functionality and must refer to accompanying documents TIP Provides you helpful hints 1 ...

Page 6: ...er process input The temperature control can be achieved by using on off or PID heat cool control strategy Control can be optimized with an auto tune feature The instrument offers a ramp to setpoint with timed soak period before switching off the output The iLD Big Display device features a large three color programmable display with capability to change a color every time the Alarm is triggered T...

Page 7: ...ply cord Furthermore to provide protection against excessive energy being drawn from the main supply in case of a fault in the equipment an overcurrent protection device shall be installed Do not exceed voltage rating on the label located on the top of the instrument housing Always disconnect power before changing signal and power connections Do not use this instrument on a work bench without its ...

Page 8: ...l or on the CD ROM enclosed with your shipment For first time users Refer to the QuickStart Manual for basic operation and set up instructions If you have the Serial Communications Ethernet Option you can easily configure the controller on your computer or on line To Disable Outputs Standby Mode is useful during setup of the instrument or when maintenance of the system is necessary When the instru...

Page 9: ...5 PART 2 SETUP 2 1 Mounting Figure 2 1 Mounting ...

Page 10: ...move back cover 2 Pass all wiring through customer drilled holes in back cover and connect wiring to terminal blocks 3 Align back cover to iLD Big Display and reinstall screws 4 Mark the location of mounting screws on the flat surface 5 Be sure to leave enough room around the bail to allow for removal and rotation of the display 6 The display can be rotated for the best viewing angle Table 2 1 Fro...

Page 11: ...OWER AC Power Connector All models INPUT Input Connector TB7 TB8 for TC models TB9 for PR Process RTD models OUTPUT 1 Based on one of the following models Relay SPDT Solid State Relay Pulse Analog Output Voltage and Current OUTPUT 2 Based on one of the following models Relay SPDT Solid State Relay Pulse OPTION Based on one of the following models RS 232C or RS 485 2 1 3 2 1 3 5 4 6 2 1 3 2 1 3 5 4...

Page 12: ...ect the main power connections as shown in Figure 2 4 Figure 2 4 Main Power Connections Figure 2 5 Inside Cover Rear View AC PWR TB1 DC PWR REMOTE PROGRAMMER TB2 TB3 1 2 3 1 2 1 2 3 4 5 L N 1 2 3 1 2 3 TB5 TB4 4 5 6 TB9 TB7 TB8 1 2 3 4 5 6 7 8 PJ3 1 2 3 4 5 6 1 3 5 2 4 6 COMMUNICATION OUTPUTS T C INPUT INPUTS OUTPUT2 OUTPUT1 RTN Rx Tx 1 2 TB5A TB5C TB5B 3 4 5 6 iLD24 OUTPUTS OUTPUT2 OUTPUT1 1 2 3 ...

Page 13: ...r select Thermocouple and Thermocouple Type in the Input Type menu see Part 3 Figure 2 6 Thermocouple Wiring Hookup TYPE Input Connector Jacket external insulation Terminal 8 Terminal 7 Extension Grade J Red White dark Brown Black K Red Yellow dark Brown Yellow T Red Blue dark Brown Blue E Red Purple dark Brown Purple N Red Orange dark Brown Brown R Red Black Green S Red Black Green B Red Gray Bla...

Page 14: ...voltage and the subtracts twice the measured drop in the lower supply current lead producing excellent lead resistance cancellation for balanced measurements The four wire RTD hookup is applicable to unbalanced lead resistance and enables the device to measure and subtract the lead voltage which produces the best lead resistance cancellation When configuring your controller select RTD type and RTD...

Page 15: ...wiring hookup for Process Voltage 0 100 mV 0 1 V 0 10 V Figure 2 9 a Process Voltage Wiring Hookup b Process Voltage Wiring Hookup with Sensor Excitation without Sensor Excitation RL Voltage limiting resistor which allows conversion of the 24 Vdc internal excitation voltage to the appropriate process input value For instance if the potentiometer value is equal to 10 kΩ the minimum RL is 14 kΩ for ...

Page 16: ... Connection are shown below Figure 2 10 a Mechanical Relay and SSR b Pulse and Analog Outputs Wiring Hookup Outputs Wiring Hookup This device may have a programmable communication output The RS 232 and RS 485 Output Connection are shown below Figure 2 11 a RS 232 Output Wiring Hookup b RS 485 Output Wiring Hookup 1 1 1 6 5 4 3 2 1 6 5 4 3 2 ...

Page 17: ...ese snubbers are internally connected between the Common C and Normally Open NO relay contacts of Output 1 and Output 2 If you have an inductive load connected between Common C and Normally Closed NC contacts of the mechanical relays and you want to protect them from the rush current during the switching period you have to connect an external snubber circuit between Common C and Normally Closed NC...

Page 18: ...ey to increase value of a parameter that is currently being modified Holding the b button down for approximately 3 seconds will speed up the rate at which the set point value increments In the Run Mode press b causes the display to flash the PEAK value press again to return to the Run Mode Press the down c button to go back to a previous Top Level Menu item Press this button twice to reset the con...

Page 19: ...15 3 2 Menu Configuration It is recommended that you put the controller in the Standby Mode for any configuration change other than Setpoints Alarms Figure 3 1 Flow Chart for ID and Setpoints ...

Page 20: ...trument will return to the Run Mode To change ID Code see ID Menu in the Configuration section ENTERING YOUR NON DEFAULT SETPOINT ID SECURITY ID NUMBER Press a 5 Display shows SP1 Setpoint 1 Menu Press a 6 Display shows SP2 Setpoint 2 Menu Press a 7 Display shows ID ID Code Menu Press d 8 Display advances to ____ Press b c 9 Use b and c to change your ID Code Press d 10 If correct ID Code is enter...

Page 21: ...tpoint 1 value Press d 5 Display shows STRD stored message momentarily and then advances to SP2 only if a change was made otherwise press a to advance to SP2 Setpoint 2 Menu SETPOINT 2 Press d 6 Display shows previous value of Setpoint 2 Press b c 7 Press b and c to increase or decrease Setpoint 2 respectively Holding b c buttons down for approximately 3 seconds will speed up the rate at which the...

Page 22: ...onfiguration Menu Press a 1 Press a if necessary until CNFG prompt appear Press d 2 Display advances to INPT Input Menu Press a 3 Pressing and releasing a to scroll through all available menus of Configuration section 3 2 4 Input Type Menu Figure 3 3 Flow Chart for Input Type Menu ...

Page 23: ...tion to T ç flashing Press d 5 Display shows STRD stored message momentarily and then T ç not flashing Press d 6 Display flashes previous thermocouple type selection i e J see below for types Press b 7 Scroll through the available thermocouple types to the selection of your choice Press d 8 Display shows STRD stored message momentarily and then advances to the RDG Reading Configuration Menu Use th...

Page 24: ...i e 392 2 see below for RTD types selection Press b 7 Scroll through the available RTD types to the selection of your choice Press d 8 Display shows STRD stored message momentarily and then advances to RTD RTD value RTD Types 392 385 Two Three or Four wire Display 392 2 392 3 392 4 385 2 385 3 385 4 Last digit indicates 2 3 or 4 wire input RTD VALUE SUBMENU Press d 9 Display flashes previous RTD v...

Page 25: ...s Process type selection i e 0 10 see below for Process types selection Press b 7 Scroll through the available Process types to the selection of your choice Press d 8 Display shows STRD stored message and then advances to RDG Reading Configuration Menu Process Types 100 mV 1 V 10 V 0 20 mA Display 0 0 1 0 1 0 0 10 0 20 For 4 20 mA Input select 0 20 mA then adjust the Input Reading accordingly To a...

Page 26: ...ure Unit selection Press b 9 Scroll though the available selections to the Temperature Unit of your choice F or C Press d 10 Display shows STRD stored message momentarily and then advances to FLTR Filter Constant FILTER CONSTANT SUBMENU Press d 11 Display flashes previous selection for Filter Constant Press b 12 Scroll though the available selections 0001 0002 0004 0008 0016 0032 0064 0128 Press d...

Page 27: ...shows Input 1 value with 1st digit flashing Press b c 16 Use b and c buttons to enter IN1 value The IN1 value min input value conversion number Disregard the position of the decimal point such that 2000 counts may actually appear as 200 0 20 00 or 2 000 Example 4 mA as 4 mA x 500 2000 Press d 17 Display advances to RD1 Reading 1 Submenu Press b c 18 Use b and c buttons to enter RD1 value This valu...

Page 28: ...splay range 10000 counts shown as 9999 See Table 3 2 below for proper conversion number Table 3 2 Conversion Table RANGE CONVERSION NUMBER 100 mV 10000 100 x 1 100 1 V 10000 1000 x 1 10 10 V 10000 1000 x 10 1 0 20 mA 10000 20 x 1 500 Example 0 1 V 0 100 0 In 1 0 Rd 1 0 Inp 2 9999 Rd 2 100 0 ...

Page 29: ...stalled If Analog Output Option is installed the controller will skip Alarm 1 Menu item to Analog Output Figure 3 5 Flow Chart for Alarm 1 ENTER ALARM 1 MENU Press a 1 Press a if necessary until CNFG prompt appears Press d 2 Display advances to INPT Input Menu Press a 3 Press a if necessary until Display advances to ALR1 Alarm 1 Menu Press d 4 Display advances to Alarm 1 ENBL Enable or DSBL Disabl...

Page 30: ...dently from Setpoint 1 If the process being monitored does not change often then Absolute Mode is recommended Deviation Mode allows changes to Setpoint 1 to be made automatically to Alarm 1 Deviation mode is typically the ideal mode if the process temperature changes often In Deviation Mode set Alarm 1 a certain number of degrees or counts away from Setpoint 1 this relation remains fixed even if S...

Page 31: ...ve BELo Below HI Lo HI Low and BAND Band Band is active if _DEV Deviation was selected Press d 14 Display shows STRD stored message momentarily and then advances to A P oN only if it was changed otherwise press a to advance to A P oN Alarm Enable Disable at Power On Submenu Above Alarm 1 condition triggered when the process variable is greater than the Alarm Hi Value Low value ignored Below Alarm ...

Page 32: ...tive while the process value is approaching Setpoint 1 ALARM 1 LOW VALUE SUBMENU Press d 17 Display flashes 1st digit of previous value Use b and c to enter new value Press b c 18 Use b and c to enter Alarm 1 Low Value Press d 19 Display shows STRD storage message momentarily and then advances to ALR H only if it was changed otherwise press a to advance to ALR H Alarm 1 Hi Value Submenu ALARM 1 HI...

Page 33: ... Output 2 Analog Output is available only if Analog Output Option board is factory installed IfAnalog Output Option is not installed the instrument will skip toAlarm 2 Menu Figure 3 6 Flow Chart for Analog Output Retransmission ENTER ANALOG OUTPUT MENU Press a 1 Press a if necessary until CNFG prompt appears Press d 2 Display advances to INPT Input Menu Press a 3 Press a if necessary until Display...

Page 34: ... Display shows STRD stored message momentarily and then advances to RD1 Submenu only if it was changed otherwise press a to advance to RD1 Reading 1 Submenu READING 1 Press d 10 Display flashes 1st digit of previous Reading 1 value Press b c 11 Enter Reading 1 value Example 0000 Press d 12 Display advances to OUT 1 Out 1 Submenu OUT 1 Press d 13 Display flashes 1st digit of previous Out 1 value Pr...

Page 35: ...put the Analog Output on 10 V FS scaled for 300 mV output range Rd1 0000 Out1 00 00 RD2 9999 Out2 00 30 The measured output will be as follows Rd1 0000 Out1 0 07 V Rd2 9999 Out2 0 23 V This means that for 300 mV output range we have 70 mV offset at zero and at full scale In order to compensate this 70 mV offset the correct scaling will be as follows Rd1 0000 Out1 00 07 Rd2 9999 Out2 00 37 The abov...

Page 36: ...log Out available only if Analog Output Option board is factory installed Figure 3 7 Flow Chart for Alarm 2 ENTER ALARM 2 MENU Press a 1 Press a if necessary until CNFG prompt appears Press d 2 Display advances to INPT Input Menu Press a 3 Press a if necessary until Display advances to ALR2 Alarm 2 Menu Press d 4 Display advances to Alarm 2 ENBL Enable or DSBL Disable Submenu Alarm must be DISABLE...

Page 37: ...FG prompt appears Press d 2 Display advances to INPT Input Menu Press a 3 Press a if necessary until Display advances to LOOP Loop Break Time Menu Press d 4 Display advances to Loop Break Time ENBL Enable or DSBL Disable Submenu and flashes the previous selection LOOP BREAK ENABLE DISABLE SUBMENU Press b 5 Scroll through the available selections ENBL or DSBL Press d 6 Display shows STRD stored mes...

Page 38: ... Adjust value 1999 to 9999 Press d 12 Display shows STRD stored message momentarily and then advances to SP DV Setpoint Deviation Menu Reading Offset Adjust C J allow the user to fine tune a minor error of the transducer however some applications may require a large offset adjust Displayed Process Value Measured Process Value R ADJ R ADJ is adjustable between 1999 to 9999 SETPOINT DEVIATION ENABLE...

Page 39: ...eter apply power to the meter CAUTION Do not proceed with TC calibration unless the above conditions have been in effect for at least one hour Press a 7 Display shows CAL1 Press d 8 Display shows flashing 0000 Press a 9 Display will still show flashing 0000 Press d 10 Display shows OUT1 meaning Calibration is complete If you accidently engage the flashing 0000 CAL alert simply re press the last bu...

Page 40: ...me contacts on the rear panel connector If Alarm 1 or Analog Output Retransmission is Enabled Output 1 is automatically Disabled Figure 3 9 Flow Chart for Output 1 It is recommended that you put the controller in the Standby Mode for any configuration change other than Setpoints Alarms ...

Page 41: ...mple setting of M50 0 of an Analog Output of 0 to 10 Vdc would produce roughly 5 Vdc at the output 8 If Self DSBL Disabled was selected display shows STRD stored message momentarily and then advances to oPLO Minimum Percent Low Submenu of Output 1 Menu There is a shorter way to Enable or Disable Self Mode From a Run Mode press d and then press a Self Mode is Enabled now Press b or c to display MXX...

Page 42: ...lay SSR Pulse or Analog Press d 15 Display flashes ON OF On Off or PID Proportional Integral Derivative Press b 16 Scroll through the available selections ON OFF or PID Press d 17 Display flashes STRD stored message momentarily and then advances to AçTN only if it was changed otherwise press a to advance to AçTN Action Type Submenu The ON OFF control is a coarse way of controlling the process The ...

Page 43: ...vailable selections Enable or Disable Press d 23 Display shows STRD stored message momentarily and then advances to ANTL only if it was changed otherwise press a to advance to ANTL Anti Integral Submenu If Enabled the controller can determine by enabling Start PID the optimum values for the three adjustments Proportional Reset and Rate corresponding to P I and D These values may be changed once th...

Page 44: ...for each 5 F over shoot increase the Proportional Band PB by 15 and for each 1 F fluctuation at the Setpoint SP increase reset by 20 Once started display shows A TUN with letters blinking in the rotating pattern When auto tune stops display will show process value Do not perform any operations or settings before first stopping Auto Tune Any alarms or other output is disabled during Auto Tune If AU...

Page 45: ...onds 000 0 399 9 If the Output 1 is Analog Option the display skips to Damping Factor CYCLE TIME SUBMENU Press d 39 Display flashes 1st digit of the previous CYCL Cycle Time value Press b c 40 Press b and c buttons to enter a new Cycle Time value 1 to 199 seconds Press d 41 Display shows STRD stored message momentarily and then advances to DPNG only if it was changed otherwise press a to advance t...

Page 46: ...ault value is 0003 For fast response time this value should be decreased while for slow response time it should be increased The DEADBAND Submenu will only appear if ON OFF was selected from the Control Type Menu DEADBAND SUBMENU Press d 45 Display flashes 1st digit of the previous DEAD Deadband value Press b c 46 Press b and c buttons to enter a new Deadband value Press d 47 Display shows STRD st...

Page 47: ...ss d 3 Display flashes ON OF ON OFF or PID PID Press b 4 Scroll through the available selections ON OFF or PID Press d 5 Display shows STRD stored message momentarily and then advances to AçTN only if it was changed otherwise press a to advance to AçTN Action Type Submenu The ON OFF control is a coarse way of controlling the Process The Dead Band improves the cycling associated with the ON Off con...

Page 48: ...d 9 Display flashes ENBL Enable or DSBL Disable Press b 10 Scroll through the available selections Enable or Disable If Enabled the PID parameter of Output 1 will be copied to Output 2 Press d 11 Display shows STRD stored message momentarily and then advances to the next submenu only if it was changed otherwise press a to advance to the next submenu If AUTO PID was ENABLED the display skips to the...

Page 49: ...of less than 7 seconds or the relays lifetime will be shortened For a cycle time of less than 7 seconds select SSR or DC pulse Use an external SSR with the DC pulse option for higher current higher than 1 Amp The DEADBAND Submenu will only appear if the ON OFF was selected from the Control Type Submenu DEADBAND SUBMENU Press d 18 Display flashes 1st digit of the previous Dead Band value Press b c ...

Page 50: ... available selections Enable or Disable Press d 6 Display shows STRD stored message momentarily and then advances to SOAK Soak Enable Disable Menu If RAMP Disable was selected display skips to the next menu item ID Code SOAK ENABLE DISABLE SUBMENU Press d 7 Display flashes ENBL or DSBL Press b 8 Scroll through the available selections Enable or Disable Press d 9 Display shows STRD stored message m...

Page 51: ...e until it reaches the original SP1 The minimum Ramp time must be at least twice the time that it will take the PV to reach the Setpoint Value SV with OUT 1 fully ON RAMP VALUE SUBMENU Press d 10 Display flashes 1st digit of previous stored Ramp Value Press b c 11 Press b and c buttons to enter a new Ramp Value Press d 12 Display shows STRD stored message momentarily and then advances to Soak Valu...

Page 52: ...s to ____ with 1st under score flashing Press b c 5 Press b and c to enter your 4 digit ID Code number Press d 6 Display advances to CH ID Change ID Code Submenu If entered ID Code is incorrect display shows ERRo Error message momentarily and then skips to the Run Mode Press d 7 Display flashes the first digit of previous entered ID Code number Press b c 8 Press b and c buttons to enter your new I...

Page 53: ...urity Level is Enabled and the user attempts to enter the Main Menu they will be prompted for an ID Code The ID Code should be correct to enter the instrument Menu item SETPOINT ID SECURITY LEVEL SUBMENU This Security Level can be functional only if FULL Security Level is Disabled Press d 17 Display flashes ENBL Enable or DSBL Disable Press b 18 Scroll through the available selections Enable or Di...

Page 54: ... configured or monitored from an IBM PC compatible computer using software available from the website or on the CD ROM enclosed with your shipment For complete instructions on the use of the Communications Option refer to the Serial Communications Reference Manual Figure 3 13 Flow Chart for Communication Option ...

Page 55: ...D Baud Submenu BAUD SUBMENU Press d 6 Display flashes previous selection for BAUD value Press b 7 Scroll through the available selections 300_ 600_ 1200 2400 4800 9600 19 2K Press d 8 Display shows STRD stored message momentarily and then advances to PRTY only if it was changed otherwise press a to advance to PRTY Parity Submenu PARITY SUBMENU Press d 9 Display flashes previous selection for Parit...

Page 56: ...t was changed otherwise press a to advance to _LF_ Line Feed submenu To select iSeries Protocol set Modbus submenu to No To select Modbus Protocol set Modbus submenu to Yes If Modbus Protocol was selected the following Communications Parameters must be set as No Parity 8 bit Data Bit 1 Stop Bit Do not attempt to change these parameters LINE FEED SUBMENU Determines if data sent from the instrument ...

Page 57: ... to MoDE Data Flow Mode Submenu DATA FLOW MODE SUBMENU Determines whether the instrument will wait for commands and data requests from the Serial Bus or whether the instrument will send data automatically and continuously to the Serial Bus Devices configured for the RS 485 Communications Standard operate properly only under Command Mode Press d 31 Display flashes previous selection for Mode Press ...

Page 58: ...ce to RDNG Reading Submenu MAIN READING SUBMENU Includes Main Reading in the data string Press d 41 Display flashes previous selection for Reading Press b 42 Scroll through the available selections NO YES Press d 43 Display shows STRD stored message momentarily and then advances to PEAK only if it was changed otherwise press a to advance to PEAK Peak Submenu PEAK VALUE SUBMENU Includes Peak Value ...

Page 59: ...it Time Interval Submenu TRANSMIT TIME INTERVAL SUBMENU This menu is applicable if Continuous Mode was selected in the Data Flow Mode Submenu and the device is configured as an RS 232C Standard device Also one or more options under the Data Format Submenu must be enabled Press d 57 Display advances to Transmit Time Value Submenu TRANSMIT TIME INTERVAL VALUE SUBMENU Determines the interval at which...

Page 60: ...ious selection for Normal Color Press b 6 Scroll through the available selections GRN RED or AMBR Press d 7 Display shows STRD stored message momentarily and then advances to 1 CLR only if it was changed otherwise press a to advance to 1 CLR Alarm 1 Display Color Submenu The menu below allows the user to change the color of display when alarm is triggered ALARM 1 DISPLAY COLOR SUBMENU Press d 8 Di...

Page 61: ...m values should be set in such a way that Alarm 1 value is always on the top of Alarm 2 value otherwise value of Alarm 1 will overwrite value of Alarm 2 and Display Color would not change when Alarm 2 is triggered Example 1 Output 1 Output 2 SSR Alarm Setup Absolute Above Alarm 2 HI Value ALR H 200 Alarm 1 HI Value ALR H 400 Color Display Setup Normal Color N CLR Green Alarm 1 Color 1 CLR Amber Al...

Page 62: ...ound the Setpoint 2 If Analog Output Option board is installed Alarm 1 is disabled only Alarm 2 is active and only two colors are available Example 4 Output 1 Relay Setpoint 1 200 Output 2 Relay Setpoint 2 200 Alarm 1 Setup Deviation Band ALR H 20 Alarm 2 Setup Deviation Hi Low ALR H 10 ALR L 5 Color Display Setup N CLR Green 1 CLR Amber 2 CLR Red Display colors change sequences AMBER RED GREEN GR...

Page 63: ...M or OFF Auto Tune Operator initiated from front panel PART 4 SPECIFICATIONS Accuracy 0 5 C temp 0 03 reading process Resolution 1 0 1 10 µV process Temperature Stability 1 RTD 0 04 C C 2 TC 25 C 77 F 0 05 C C Cold Junction Compensation 3 Process 50 ppm C NMRR 60 dB CMRR 120 dB A D Conversion Dual slope Reading Rate 3 samples per second Digital Filter Programmable Display 4 digit or 6 digit 7 segm...

Page 64: ...e configured as Alarm 1 output Output 2 SPDT type can be configured as Alarm 2 output SSR 20 265 Vac 0 05 0 5 A Resistive Load continuous DC Pulse Non Isolated 10 Vdc 20 mA Analog Output Output 1 only Non Isolated Proportional 0 to 10 Vdc or 0 to 20 mA 500 Ω max COMMUNICATIONS optional RS 232 or RS 485 programmable 300 to 19 2 K baud complete programmable setup capability program to transmit curre...

Page 65: ... 0 5 C 58 to 104 F 1 8 F 104 to 3250 F 0 9 F 50 to 100 C 1 0 C Pt 10 Rh Pt 100 to 1768 C 0 5 C 58 to 212 F 1 8 F 212 to 3214 F 0 9 F 200 to 640 C 1 0 C 30 Rh Pt 640 to 1820 C 0 5 C 6 Rh Pt 212 to 1184 F 1 8 F 1184 to 3308 F 0 9 F 5 Re W 0 to 2354 C 0 4 C 26 Re W 32 to 4253 F 0 7 F 250 to 100 C 1 0 C Nicrosil Nisil 100 to 1300 C 0 4 C 418 to 148 F 1 8 F 148 to 2372 F 0 7 F J 200 to 900 C 0 4 C DIN ...

Page 66: ...arm 1 only Alarm Low ALR L 100 0 Alarm High ALR H 400 0 LOOP Loop Break Time LOOP Disable DSBL Loop Value B TIM 00 59 Reading Adjust Value R ADJ 000 0 ANALOG OUTPUT Retransmission Analog Output ANLG Enabled ENBL Current Voltage CURR VOLT Voltage VOLT Scale and Offset Reading 0 999 9 cts Output 0 10 V OUTPUT 1 2 Self SELF Disabled DSBL Output 1 only Low Value LO 0000 Output 1 only High Value HI 009...

Page 67: ...d Rate BAUD 9600 Parity PRTY Odd Data bit DATA 7 bit Stop Bit 1 bit Modbus Protocol M BUS No Line Feed LF No Echo ECHO Yes Standard Interface STND RS 232 232C Command Mode MODE Command CMD Separation SEPR Space SPCE Alarm Status STAT No Reading RDNG Yes Peak No Valley VALY No Units UNIT No Multipoint Address ADDR 0001 Transmit Time TR TM 0016 Display Color COLR Normal Color N CLR Green GRN Alarm 1...

Page 68: ...Port L PE Performance 1 0 kV DC Port L L Criteria B 2 0 kV DC Port L PE Radio Frequency 0 15 80 MHz IEC 1000 4 6 conducted 3 Vrms Performance 80 AM 1 KHz Criteria A This instrument complies with the following EMC Emission Standards as tested per EN 61326 2 1998 Class B equipment Phenomena Frequency Limits Basic Range Standard Radiated 30 230 MHz 30 dB_V m at 10 m CISPR 22 Emission 230 1000 MHz 37 ...

Page 69: ...NOTES 65 ...

Page 70: ...ONS Equipment sold by OMEGA is not intended to be used nor shall it be used 1 as a Basic Component under 10 CFR 21 NRC used in or with any nuclear installation or activity or 2 in medical applications or used on humans Should any Product s be used in or with any nuclear installation or activity medical application used on humans or misused in any way OMEGA assumes no responsibility as set forth in...

Page 71: ...icators Turbine Paddlewheel Systems Totalizers Batch Controllers pH CONDUCTIVITY pH Electrodes Testers Accessories Benchtop Laboratory Meters Controllers Calibrators Simulators Pumps Industrial pH Conductivity Equipment DATA ACQUISITION Data Acquisition Engineering Software Communications Based Acquisition Systems Plug in Cards for Apple IBM Compatibles Datalogging Systems Recorders Printers Plott...

Reviews: