(model
060
)
5
installation manual
Copper Pipe for Air Conditioner
Pipe Material
Size(mm)
J(Gas side)
Mode(R410A)
018
024
036 - 060
Φ12.7
I(Liquid side)
Φ6.4
Φ15.9
Φ6.4
Φ9.5
Φ15.9
5. INSTALL THE CONNECTING PIPE
Do not let air, dust, or other impurities fall in the pipe system
during the time of installation.
The connecting pipe should not be installed until the indoor and
outdoor units have been fixed already.
Keep the connecting pipe dry, and do not let moisture in during
installation.
The temperature of refrigerant circuit will be high, please keep
the interconnection cable away from the copper tube.
CAUTION
The dimension of the unit (Unit: mm)
4.4
Hanging arm
Mounting bolt
Hanging
screw bolt
Hanging
screw bolt
(model
018 - 048
)
Hanging
screw bolt
D. Connecting point of
refrigerant pipe
(D.gas side)
Drain point
E. Connecting point of
refrigerant pipe
(E. Liquid side)
Fig. 4-13
The figures above are based on model 18 as rated
capacity,which may differ from the unit you purchased.
Table 4-1
20mm
1670 680 244 1070 450 1542 200
1670 680 285 1070 380 1613 220
MODEL
018
024
036 / 048
060
A
B
D
E
F
G
C
990 660 203 505 506 907 200
1280 660 203 795 506 1195 200
CAUTION
G
C
3.Hang the unit on the hanging arm by sliding backward. Securely
tighten the mounting bolts on both sides.
Table 4-2
4.5 Material and size of the piping
5.1 The Procedure of Connecting Pipes
5.1.1 Measure the necessary length of the connecting pipe, and
make it by the following way.
1) Connect the indoor unit at first, then the outdoor unit.
a. Bend the tubing in proper way. Don,t harm them.
1. Daub the surfaces of the flare pipe and the joint nuts with
frozen oil, and wrench it for 3~4 rounds with hands before
fasten the flare nuts.
2. Be sure to use two wrenches simultaneously when you
connect or disconnect the pipes.
CAUTION
2) The stop valve of the outdoor unit should be closed
absolutely (as original state). Every time you connect it, first
loosen the nuts at the part of stop valve, then connect the flare
pipe immediately (in 5 minutes). If the nuts have been loosened
for a long time, dusts and other impurities may enter the pipe
system and may cause malfunction later. So please expel the
air out of the pipe with refrigerant before connection.
3) Expel the air (refer to the “Expel The Air”) after connecting
the refrigerant pipe with the indoor unit and the outdoor unit.
Then fasten the nuts at the repair-points.
Notices For Benable pipe.
The bending angle should not exceed 90°.
Bending position is preferably in the bendable pipe. The
larger the better it is .
Do not bend the pipe more than three times.