5. Electric Characteristics
Model
Power Supply
1
Compressor
OFM
Capacity
Hz
Volts
Min.volts
Max.volts MCA
2
TOCA
3
MFA
4
MSC
5
RLA
6
kW
FLA
50 220-240
198
264
8.8
10
16
/
5.6
0.02
0.6
ICHD012-DMG035
50 220-240
198
264
8.8
10
16
/
5.8
0.02
0.6
ICHD018-DMG053
50 220-240
198
264
12.9
14.5
20
/
7.85 0.05
6
0.71
ICHD024-DMG071
50 220-240
198
264
17.5
20
25
/
8.85 0.08
1.0
ICHD031-DMG090
50 220-240
198
264
23
25
32
/
11.8 0.08
1.0
ICHD036-DMG105
50 220-240
198
264
27
28.5
32
/
14.5 0.17 1.53
ICHD042-DMG120
50 220-240
198
264
27
28.5
32
/
23
0.17 1.53
ICHD048-DMG140
50 220-240
198
264
32
35.2
40
/
27.5 0.17 1.53
ICHD060-DMG160
50 220-240
198
264
33
35
40
/
27.1 0.17 1.53
Abbreviations:
MCA: Minimum Circuit Amps; TOCA: Total Over-current Amps; MFA: Maximum Fuse Amps; MSC: Maximum Starting Current (A); RLA:
Rated Load Amps; FLA: Full Load Amps
Notes:
1. Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits. Maximum
allowable voltage variation between phases is 2%.
2. Select wire size based on the value of MCA.
TOCA indicates the total overcurrent amps value of each OC set.
MFA is used to select overcurrent circuit breakers and residual-current circuit breakers.
MSC indicates the maximum current on compressor start-up in amps.
RLA is based on the following conditions: indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB.
ICHD009-DMG026
Summary of Contents for OTEC IEMP-D Series
Page 1: ...IEMP D Series Ducted Fan Coil Technical Manual...
Page 4: ...2 Part 1 General information 1 Model Names of Indoor Outdoor Units 3 2 External Appearance 4...
Page 17: ...17 ICHD031J0A DMG090...
Page 18: ...18 ICHD036J0A DMG105 ICHD042J0A DMG120 ICHD048J0A DMG140...
Page 19: ...19 ICHD060J0A DMG160...
Page 29: ...36 IEMP031J3A DCG090 IEMP060J3A DCG160...
Page 30: ...37 IEMP036J3A DCG105 IEMP042J3A DCG120 IEMP048J3A DCG140...
Page 86: ...126 IEMP031 36 42 48 60 J3A DCG090 105 120 140 160...