130
P43
Compressor phase loss protection
Immediate display, spot check
P44
Compressor zero speed protection
Immediate display, spot check
P45
Outdoor 341 main chip drive synchronization fault
Immediate display, spot check
P46
Compressor stall protection
Immediate display, spot check
P47
Compressor lock protection
Immediate display, spot check
P48
Compressor out-synchronous protection
Immediate display, spot check
P49
Compressor over-current protection
Immediate display, spot check
P6
Compressor high discharge temperature protection
Immediate display, spot check
P8
Outdoor electric control current protection
Immediate display, spot check
P80
IDU current protection
Immediate display, spot check
P81
ODU current protection
Immediate display, spot check
P82
Input AC current sampling circuit fault
Immediate display, spot check
PA
High temperature protection of condenser
Immediate display, spot check
PF
PFC switch power-off
Immediate display, spot check
P9
Evaporator high and low temperature protection
Code will not be displayed, but can be queried
P90
Evaporator high temperature protection
Code will not be displayed, but can be queried
P91
Evaporator low temperature protection
Code will not be displayed, but can be queried
L0
Evaporator high and low temperature frequency limit
Code will not be displayed, but can be queried
L1
Condenser high temperature frequency limit
Code will not be displayed, but can be queried
L2
Compressor discharge high temperature frequency limit
Code will not be displayed, but can be queried
L3
Current frequency limit
Code will not be displayed, but can be queried
L4
Voltage frequency limit
Code will not be displayed, but can be queried
L6
PFC fault frequency limit
Code will not be displayed, but can be queried
IEMP031(36,42,48,60)J3A-DCG090(105,120,140,160)
Error code
Error or protection definition
Error display
HF
IDU mismatching error
Immediate display, spot check
H4
L (L0/L1) error occurs three times in one hour, reporting H4,
and this error is not recoverable.
After H4 error, spot check may be performed on the latest
three L errors (not limited to L0, L1). For example: report L0-
L4-L8-L9-L0-L1 within one hour, and report H4 error.
The errors for spot check are L9, L0, and L1.
Immediate display, spot check
E7
IDU EEPROM error
Immediate display, spot check
E9
ODU EEPROM error
Immediate display, spot check
E.9.
Wrong compressor model in parameter memory EPROM
Immediate display (display E9), spot check
available
H0
Communication error between main control board and IR341 Immediate display, spot check
E1
Communication error between IDU and ODU
Immediate display, spot check
E2
T1 sensor error
Immediate display, spot check
E3
T2 sensor error
Immediate display, spot check
E4
T2B sensor error
Immediate display, spot check
E43
T3 sensor error
Immediate display, spot check
E44
T4 sensor error
Immediate display, spot check
E45
T5 sensor error
Immediate display, spot check
E5
Voltage protection error
After continuing 10 minutes Indoor unit
displays, spot check available
Summary of Contents for OTEC IEMP-D Series
Page 1: ...IEMP D Series Ducted Fan Coil Technical Manual...
Page 4: ...2 Part 1 General information 1 Model Names of Indoor Outdoor Units 3 2 External Appearance 4...
Page 17: ...17 ICHD031J0A DMG090...
Page 18: ...18 ICHD036J0A DMG105 ICHD042J0A DMG120 ICHD048J0A DMG140...
Page 19: ...19 ICHD060J0A DMG160...
Page 29: ...36 IEMP031J3A DCG090 IEMP060J3A DCG160...
Page 30: ...37 IEMP036J3A DCG105 IEMP042J3A DCG120 IEMP048J3A DCG140...
Page 86: ...126 IEMP031 36 42 48 60 J3A DCG090 105 120 140 160...