The display will show “
1o-
x
”. To set the output mode, scroll through the
options by pressing the
adjusting
key
until the setting matching the
desired output is displayed. Use the following table to set the output mode
of Out 1.
Once the desired setting is displayed, press the
setting
key
. The displayed
setting will be entered and the next parameter setting, (high setpoint for out1
parameter) will be displayed.
Mode
Output 1
Menu
Selection
Actuation
1 Hysteresis
Active
Low
1o-1
Turns the output off when the pressure has reached the high
setpoint (green line). The output remains off until the
pressure has dropped below the low setpoint (blue line).
2 Hysteresis
Active
High
1o-2
Turns the output on when the pressure has reached the high
setpoint. The output remains on until the pressure has
dropped below the low setpoint.
3
Window
Active
Low
1o-3
Turns the output off when the pressure is between the high
setpoint (green line) and the pressure low setpoint (blue line).
4
Window
Active
High
1o-4
Turns the output on when the pressure is between the high
setpoint (green line) and the pressure low setpoint (blue line).
High Setpoint
The next parameter encountered is for setting the high setpoint (green
line on above graph) for
output 1
. The display will quickly flash “1H” and
then it will display the current value of the high setpoint.
To set the high setpoint, increment the current digit (flashing) by pressing the
adjusting
key
until the display matches the desired setpoint. The digit will reset
to zero (roll over) after nine has been reached in case the desired number has been
accidentally passed. To scroll to the next digit, press the
carry
key
. Once the
rightmost digit has been set, press the
setting
key
to go to the next parameter.
Low Setpoint
The next parameter encountered is for setting the low setpoint (blue
line on the graphs) for
output 1
. The display will quickly flash “1L” and
then it will display the current value of the low setpoint. This value is
entered exactly like the high setpoint, discussed above.
Once the rightmost digit has been set, press the
setting
key
to go to the next
parameter.