4.3.7 Sensor Setup (continued)
Offset:
If it is determined that the readings are slightly off, the user can manually assign
numerical values to adjust the readings for temperature (in ºC) , humidity (in
percentage), and barometric pressure (in mbar). The offset value can either be a positive
or a negative number with one decimal point.
Update:
Saves changes
Reset Value:
Ignores changes and puts previous values back in the fields.
Cancel:
Ignores all the changes and goes back to the "Sensor Setup" page.
Reset Sensor:
Reset the End Device readings and status. If the End Device is not on
the network, the data will be cleared after about 3 minutes. Otherwise, the End Device
will reset itself and re-join the network after a minute.
Identify:
INACTIVE: End device is in running mode and sending data to the Coordinator
periodically. ACTIVE: End device is in identify mode and it keeps its blue LED on solid
so that operator can identify the corresponding sensor easily.
Once you click on the “Identity” button (“Active” Status) to locate your End
Device you need to make sure to click on the button again to make it “Inactive”;
otherwise the blue LED will stay solid until the battery is discharged.
Select Another Group
: Go back to the group selection page to setup sensors.
Figure 4.17b Sensor Parameters for Thermocouple Option
SENSOR PARAMETERS
Sensor #6, Group A
SENSOR PARAMETERS
http://192.168.1.200
Address
Main Menu
Sensor Name
OVEN5
Select Another Group
Identify: INACTIVE
Reset Sensor
Cancel
Update
Periodic
10
Update
Reset Value
(seconds)
Offset1 (xxxx.x) 0
Offset3 (xxxx.x) 0
TC type
K type
TC type
K type
Cold Junction Compensation for Ch1
Cold Junction Compensation for Ch2
(C)
(C)
46