Cod. 710.0103.01.00 Rev2A – 11.2012
16 - 111
7.0 TROUBLESHOOTING
SYMPTOM
POSSIBLE ORIGIN
SOLUTION
A) Temperature
shown in display
higher than the preset
value.
•
High compressed air inlet temperature.
•
High compressed air flow.
•
High ambient temperature.
•
Fouler refrigerant condenser.
•
Low refrigerant charge.
•
Phases connected incorrectly.
•
Faulty refrigerant compressor.
•
Faulty fan.
•
Faulty fan pressure switch or thermostat.
•
Faulty electronic controller
•
Reduce air temperature to within design limits.
•
Reduce air flow to within design limits.
•
Increase ventilation rate of installation area.
•
Clean condenser.
•
Locate and repair leak and re-charge.
•
Connect the phases correctly.
•
Replace item.
•
Replace item.
•
Replace item.
•
Replace item.
B) Excessive air
pressure drop across
dryer.
•
Inlet / outlet piping reversed.
•
Temperature probe out of well.
•
Faulty refrigerant solenoid valve.
•
Ambient temperature below freezing.
•
Obstruction in air circuit.
•
Air by – pass valve closed.
•
Connect properly.
•
Re-install.
•
Replace item.
•
Install dryer in heated space.
•
Locate and remove blockage.
•
Open valve.
C) Water present in air
downstream of dryer.
•
Condensate drain strainer fouled.
•
Faulty condensate drainer.
•
Faulty electronic controller.
•
High dew – point temperature.
•
Air by – pass valve open.
•
Clean strainer.
•
Replace item.
•
Replace item.
•
See Symptom #A above.
•
Close valve.
8.0 CONDENSATE DRAIN
8.1 Drain valve maintenance
•
Close the ball valve located on the filter/stop installed at the drain trap inlet.
•
Depressurize the trap by pushing the TEST button on the control panel.
•
Unscrew the plug in the end of the filter/stop to access the filter screen (F) and
clean it with a compressed air jet.
•
Reassemble and open filter/stop valve.
Cleaning of the drain solenoid valve
8.2 NO LOSS CONDENSATE DRAIN
Electronic drain discharge is the new discharger applicable
to any compressed air systems. It eliminates the
condensate without wasting compressed air.
Electronic drain discharge starts automatically, without the
need of any adjustment. The condensate discharge occurs
to the use of an electronic sensor, which detects the
amount of condensate in the integrated water collecting
tank. The level sensor drives start and duration of the
drainage, so preventing any wasting of compressed air.
At the end of installation, put the system under pressure
and push the TEST key repeatedly to eliminate the air
bubbles contained in the discharger inlet fittings.
To this discharger will be applied the Beko warranty
conditions.
(F)
Summary of Contents for ED 1300
Page 2: ...1 113 ...
Page 4: ...5 113 ...
Page 115: ...Cod 710 0103 01 00 Rev2A 11 2012 111 111 SLI VB SC FF VG IM TH G VT ...
Page 116: ......