CF38
EEprom parameters map
1
Pr2
Password
SD
N.U.
---
---
ES
N.U.
---
---
CO01
Minimum delay at compressor re-start
sec 10x
18
CO02
Minimum delay for compressor stop
sec10x
18
CO
CO05
Delay at Refrigerant Compressor start form Power ON
Min.10x
48
Refrigerant
compressor
CO12
Refrigerant Compressor 1
0 = ON
1 = OFF
0
parameters
CO14
Refrigerant Compressor hour counter SET (SUGGESTED
MAINTENANCE)
h 10x
0
Pr2
Password
FA
N.U.
---
---
Ar
N.U.
---
---
AL01
Digital input low pressure alarm delay
Sec
5
AL02
Low pressure digital input Max. number of activations / hour
5
AL03
Low pressure alarm with dryer in remote OFF status or stand-by
0 = alarm detection OFF
1 = alarm detection ON
1
AL08
Refrigerant compressor thermal protection alarm delay at start
Sec
1
AL09
Refrig. compressor thermal protection Max. number of activations / hour
16
AL10
Refrigerant compressor thermal protection alarm rest after AL09
0
AL11
High temperature alarm Set point PB3 (AMBIENT)
°C
45
AL12
High temperature Differential PB3 (AMBIENT)
°C
5
AL13
High temperature alarm delay PB3 (AMBIENT)
Min
15
AL
Alarm
parameters
AL17
Active output contact for remote output relay
0= alarm output ON
1= alarm output OFF
0
AL18
Alarm relay polarity
0= active output close contact
1= active output open contact
0
AL19
Low temperature alarm delay PB1 (DEW POINT)
Min
5
AL20
Low temperature alarm Set PB1 (DEW POINT)
°C
-0,5
AL21
Low temperature alarm differential PB1 (DEW POINT)
°C
3
AL22
High temperature alarm delay PB1 (DEW POINT)
Min
10
AL23
High temperature alarm Set point PB1 (DEW POINT)
°C
15
AL24
High temperature alarm differential PB1 (DEW POINT)
°C
2
AL25
High temperature alarm delay PB2 (AIR INLET)
Min
20
AL26
High temperature alarm Set point PB2 (AIR INLET)
°C
60
AL27
High temperature alarm differential PB2 (AIR INLET)
°C
10
AL28
High temperature alarm delay PB4 (REFRIGERANT SUCTION)
Min
20
AL29
High temperature alarm Set point PB4 (REFRIGERANT SUCTION)
°C
45
AL30
High temperature alarm differential PB4 (REFRIGERANT SUCTION)
°C
5
AL31
Alarm Probe PB1 - Max. number of activations / hour
5
AL32
Alarm Probe PB2 - Max. number of activations / hour
5
AL33
Alarm Probe PB3 - Max. number of activations / hour
5
AL34
Alarm Probe PB4 - Max. number of activations / hour
5
AL35
Numero massimo interventi ora allarme generico utente
5
AL36
Delay temperature alarm signalling from compressor start
Min
2
Pr2