background image

 

Cod. 710.0201.01.00 Rev.01 

– 05.2022 

© Copyright 2022 OMI Srl - All rights reserved

 

9 - 11 

 

 

 

TROUBLE 

DISPLAY 

POSSIBLE CAUSE 

REMEDY 

WAT

ER IN T

HE SYSTEM

 

Control panel 

display is 

blank 

No power in the line. 

Restore the power in the line. 

Problems with cabling. 

Check cabling; if the trouble persists, replace it. 

Problems with the electronic control board. 

Check the electronic control board; if the trouble persists, 
replace it. 

 

The dryer is off. 

Turn it on by pressing the ON/OFF switch for 1 second. 

 

Dryer in stand-by. 

Wait 2 minutes after the dryer is switched on. 

Compressed air inlet/outlet inverted. 

Check if the compressed air inlet/outlet is connected 
properly. 

The flow rate and/or temperature of the air 
entering the dryer are higher than the 
nominal values. 

Restore the nominal conditions. 

The ambient temperature is higher than the 
nominal values. 

Restore the nominal conditions. 

The condenser is dirty. 

Clean the condenser. 

Condensate drain is not functioning. 
Pic.3 

Clean the condensate drainage system filter mesh. 

Replace the coil of the drainage solenoid valve if burned. 

Clean or replace the drainage solenoid valve if 
clogged/jammed. 
Check the C8 and C9 parameters of the electronic control 
board; if the trouble persists, replace it. 

Condensate drain is not functioning. 
Pic.4-5 

Check the no loss condensate drain; if the trouble persists, 
replace it. 

The temperature control probe is positioned 
improperly or faulty. 

Check the probe; if the trouble persists, replace it. 

 

 

Problems with cabling or with the electronic 
control board. 

Check the cabling and the electronic control board, if the 
trouble persists, replace them. 

Activation of compressor’s internal thermal 
protection. 

Wait one hour and check again. If the fault persists: stop 
dryer and call your localOMI distributor. 

 

 

Problems with the electrical components of 
the compressor. 

Check the electrical components of the compressor. 

Defective compressor. 

Replace the compressor. 

The flow rate and/or temperature of the air 
entering the dryer are higher than the 
nominal values. 

Restore the nominal conditions. 

The ambient temperature is higher than the 
nominal values. 

Restore the nominal conditions. 

The condenser is dirty. 

Clean the condenser. 

The temperature control probe is positioned 
improperly or faulty. 

Check the probe; if the trouble persists, replace it. 

Fan pressure switch defective or burned out 
(if present). 

Turn off the dryer and call your localOMI distributor. 

High pressure switch defective or burned out 
(if present). 

Turn off the dryer and call your localOMI distributor. 

Gas leakage in the refrigerating circuit. 

Turn off the dryer and call your localOMI distributor. 

Defective fan. 

Replace the fan. 

Protection fuse burned out (if present). 

Replace the fuse. 

 

The temperature control probe is positioned 
improperly or faulty. 

Check the probe; if the trouble persists, replace it. 

Gas leakage in the refrigerating circuit 
without load. 

Turn off the dryer and call your localOMI distributor. 

 

The temperature control probe is positioned 
improperly or faulty. 

Check the probe; if the trouble persists, replace it. 

 

Series of alarms very close to each other. 

Call your localOMI distributor. 

 
 
 
 
 
 
 
 
 
 

Summary of Contents for ED88 HP45

Page 1: ...Cod 710 0201 01 00 Rev 01 05 2022 Copyright 2022 OMI Srl All rights reserved 1 11 DIRECT EXPANSION COMPRESSED AIR DRYERS Operators Manual ED HP45 88 108 180 225 270 360 480 660 990 1200...

Page 2: ...Cod 710 0201 01 00 Rev 01 05 2022 Copyright 2022 OMI Srl All rights reserved 1 11...

Page 3: ...te discharge parameters programming 6 3 1 3 Anomaly warning 6 3 1 4 Remote signalling alarm 7 3 2 Before start up 7 3 3 Start up 7 4 MAINTENANCE TROUBLESHOOTING AND DISMANTLING 4 1 Maintenance 8 4 2 T...

Page 4: ...Cod 710 0201 01 00 Rev 01 05 2022 Copyright 2022 OMI Srl All rights reserved 3 11...

Page 5: ...electric shock Condensate drain point Rotation direction of the fan Pay particular attention to the risk of moving parts Explosion risk Lifting point Don t lift from this point Attention Before perfor...

Page 6: ...rs counterflow the initial air air exchanger and it is reheated by the inlet hot air with the consequence of energy recovering and also reduction of the relative humidity contained in the outflowing a...

Page 7: ...tempt to lift heavy objects without proper lifting equipment i e crane hoist slings or fork truck Lifting any unit without proper lifting equipment may cause serious injury Use fork lift channels wher...

Page 8: ...it is necessary to install a protective device to protect the equipment at high temperature from the risk of exceeding the maximum allowable temperature The dryer is equipped with a safety valve freo...

Page 9: ...en pushed while setting the drain set point it decreases the displayed value of one unit per second during the first 10 seconds than of one unit every 0 1 sec When pushed for 10 seconds during normal...

Page 10: ...amiliar with the operation of the dryer WARNING FOR USER IT S FORBIDDEN TO ATTEMPT TO MODIFY THE OTHER CONFIGURATION PARAMETERS OF THE ELECTRONIC CONTROLLER WITHOUT AUTHORIZATION AND COLLABORATION OFO...

Page 11: ...eration and it doesn t require any calibration Nevertheless it s necessary to check the operating performances during the first working hours 3 3 START UP The operations specified below must be perfor...

Page 12: ...eck the condition of any filters installed with the dryer Replace elements as needed YEARLY OR EVERY 2000 HOURS OF OPERATION Check if the flexible tube used for condensate drainage is damaged and repl...

Page 13: ...t Problems with cabling or with the electronic control board Check the cabling and the electronic control board if the trouble persists replace them Activation of compressor s internal thermal protect...

Page 14: ...ondensate drainage Drainage solenoid valve jammed clean or replace it Verify the condensate drainage times set on the electronic control board C8 and C9 Check the signal from the control board if it i...

Page 15: ...electricity supply to the dryer and then affix appropriate warning signs to avoid the machine being reconnected to the electricity mains Please consult the contents and the safety instructions in the...

Page 16: ...reset Welding Joints Coefficient z 0 7 Table 5 6 1 Tickness allowance c 0 mm For copper Not required for surfaces in contact with freon EN 14276 1 c 1 mm For carbon steel Manufacturer design code 717...

Reviews: