43
Power transformers
For the measurement of C
L
the setup has to be changed. The HV output has to be connected to the LV
side and IN A to the HV side (see Figure 5-4 blow).
Figure 5-4:
CP TD1
connected to a two-winding transformer for the measurement of
C
HL
and C
L
With this setup 3 configurations are available as well (see Table 5-2 below). As C
HL
has been measured
before, usually only C
L
is measured in this second measurement.
Table 5-2: Modes available with a measurement setup as seen in Figure 5-4
Mode
IN A
Ground
Result
UST-A
Measured
Guarded
C
HL
GSTg-A or GSTg-(A+B) Guarded
Measured
C
L
GSTg-B
Measured
Measured
C
HL
+ C
L
CP TD 1
LV
HV
C
HL
C
L
C
H
IN A
IN B
HV output