Measurements on three-winding transformers
In IEEE Std. 62-1995
[1]
the test procedure is described for transformers with two and three windings.
Figure 5-12 shows the six measurements necessary for a three-winding transformer.
Figure 5-12: Three-winding transformer test according to IEEE 62-1995
A more detailed test procedure for 2- and three-winding transformers can be found in IEEE C57.12.90
[2]
1. ANSI Standard 62-1995: "IEEE Guide for Diagnostic Field testing of Electric Power Apparatus - Part 1: Oil Filled Power
Transformers, Regulators, and Reactors", IEEE New York, 1995
Table 5-8: The six necessary measurements
Test mode
Energize
Ground
Guard
UST
Measure
GST
High (HV)
-
Low, Tertiary
-
C
H
GST
Low (LV)
-
Tertiary, High
-
C
L
GST
Tertiary (TV)
-
High, Low
-
C
T
Supplementary Test for inter-winding insulations
UST
High (HV)
Tertiary (TV)
-
Low (LV)
C
HL
UST
Low (LV)
High (HV)
-
Tertiary (TV)
C
LT
UST
Tertiary (TV)
Low (LV)
-
High (HV)
C
HT
2. IEEE Standard C57.12.90: "IEEE Standard Test Code for Liquid-Immersed Distribution, Power, and Regulating
Transformers", IEEE New York, 1995
Tertiary
Low
High
C
HT
C
LT
C
HL
C
T
C
L
C
H