Technical Data
16 - 7
400A DC output
While using the
400A DC
output, disconnect any cables that may be plugged in
to the
800A AC
output. These outputs are internally connected.
Table 3:
400A DC
output
technical data
400A DC output
Connection
10mm connectors
Insulation
Internally connected to the
800A AC
output, insulated
against all other inputs and outputs.
Voltage with reference to earth must not exceed
300V
rms
and 420V
peak
on either socket.
Reinforced insulation against mains power supply, all
interfaces and other safety low-voltage circuits.
Output power at:
typ. power P
max
typical time t
max
400A
300A
200A
100A
2600W
1950W
1300W
630W
140s
3min
> 2hrs
>> 2hrs
Measurement
Internal precision current measurement from
0 ... 400A DC
Abs. max. rating: limited through output
Accuracy:
typ. error < ± 0.2% (rd) ± 0.05% (fs),
guaranteed < ± 0.4% (rd) ± 0.1%(fs)
Resolution:
Measurement
Display
100 mA/bit
10 mA
Connection:
internally connected
Summary of Contents for CPC 100
Page 12: ...CPC 100 V1 41 x...
Page 28: ...CPC 100 V1 41 1 16...
Page 90: ...CPC 100 V1 41 3 14...
Page 194: ...CPC 100 V1 41 6 30...
Page 250: ...CPC 100 V1 41 8 32 Figure 24 Settings of Amplifier test card for this example use case...
Page 258: ...CPC 100 V1 41 9 4...
Page 264: ...CPC 100 V1 41 10 6...
Page 282: ...CPC 100 V1 41 12 10 Figure 9 Saving tests with the CPC Editor...
Page 284: ...CPC 100 V1 41 12 12...
Page 312: ...CPC 100 V1 41 14 12...
Page 316: ...CPC 100 V1 41 15 4...
Page 350: ...CPC 100 V1 41 16 34...
Page 372: ...OMICRON Contact Addresses 22...