1
Introduction
1.1 Scope of delivery
The following accessories are part of the
VBO3
standard delivery but can also be ordered separately:
Accessory
Quantity
Order number
Connection cable
VBO3
to CMC, 4-pole, 1 m length
2
VEHK0053
Connection cable
VBO3
to test object, 4-pole, 3 m length
1
VEHK0054
Flexible jumpers
4
VEHZ0009
Module bag
1
VEHP0031
Before operating
VBO3
for the first time, use the shipping documents to verify that all accessories are
available.
1.2 Designated use
VBO3
is a voltage transformer and used as an accessory for OMICRON's CMC test sets. The device
is intended for use with CMC test sets only.
VBO3
transforms a CMC's output voltages of 0 ... 300 V to
0 ... 600 V.
Therefore, you can use CMC test sets for testing the V>> stage of LOM protection at wind power
stations. Their threshold is at least 460 V (nominal voltage in wind power stations is 690 V L-L
(398.37 V L-E)). You can also test other renewable energy systems such as biogas, photovoltaic,
small hydroelectric power as well as combined heat and power plants.
Furthermore, you can test industrial networks with voltage levels > 300 V.
Disclaimer
The advisory procedures and information contained within this user manual have been compiled as a
guide to the safe and effective operation of
VBO3
. It has been prepared in conjunction with application
engineers and the collective experience of the manufacturer.
The in-service conditions for the use of
VBO3
may vary between customers and end-users.
Consequently, this user manual is offered as a guide only. It shall be used in conjunction with the
customer’s own safety procedures, maintenance program, engineering judgment, and training
qualifications.
If
VBO3
is used in a different manner than described in this user manual, the protection provided by
VBO3
may be impaired, and this may result in damage to property or persons.
1.3 Declaration of conformity (EU)
The equipment adheres to the guidelines of the council of the European Community for meeting the
requirements of the member states regarding the low voltage directive (LVD) and the RoHS directive.
Introduction