OMNI 4000/7000 Operations and Maintenance Guide
– Rev F
7-15
Maintenance
Reset Single Channel Calibration
To reset the channel if you have trouble calibrating an individual analog input or output channel,
follow these instructions:
1.
Click the
Diagnostics
button in the Home
ribbon to open the
Diagnostics
tree in the
left panel.
Select
System Resets
in the left panel and
then select the
Reset Calibration
tab in
the screens to the right.
2.
In the
Reset Individual Calibration
Constants
section of the
Reset
Calibration
screen:
a. Select the
Type
radio button for the
channel.
b. Input the channel number in the
Number
field.
c. Click
Reset Calibration Constants
.
3.
At the prompt, click
Yes
to reset the
channel.
4.
After you reset the channel, you can
attempt to calibrate the channel again. You
can do this either through OMNICONNECT
(Section 7.2.2) or the front panel
(Section 7.3.2).