OMNI 4000/7000 Operations and Maintenance Guide
– Rev F
7-16
Maintenance
5.
If the problem persists:
a. Check the hardware jumper settings
for the channel in question.
b. Check the software configuration
settings to verify that they are set to
the same type of input or output as the
hardware jumpers.
c. Contact the OMNI Help Desk at
+1 281-240-6161.
Reset Multiple Channel Calibration
Use the option to reset multiple channels when:
•
Project-specific requirements necessitate resetting all channels before beginning calibration.
•
Multiple input or output channels will not calibrate correctly.
To reset multiple channels simultaneously, follow these instructions:
1.
For multiple calibration resets, click the
appropriate button:
•
Reset All Calibration
for resetting all
Inputs and Outputs
•
Reset All Process Inputs
for resetting
analog inputs only
•
Reset All Analog Outputs
for
resetting analog outputs only
2.
At the prompt, click
Yes
to reset
multiple channels.
3.
After you reset the channels, you can
attempt to calibrate them again. You can
do this either through OMNICONNECT
(Section 7.2.2) or the front panel
(Section 7.3.2).
4.
If the problem persists:
a. Check the hardware jumper settings
for the channel in question.
b. Check the software configuration
settings to verify that they are set to
the same type of input or output as the
hardware jumpers.
c. Contact the OMNI Help Desk at
+1 281-240-6161.