4.1 The RMT Telegrams (Receive Message Telegram)
4.1.1
Gateway Message changed its Baud Mode (RMT Receive Message Telegram)
This telegram is sent by the gateway to the Master after the baud
rate has changed. The baud rate is set by means of plug-in jumpers
at the gateway.
DB0 (BM) -> New baud rate value
Status (BM) -> 1 = 9.6 kBaud
Status (BM) -> 2 = 19.2 kBaud
Status (BM) -> 3 = 38.4 kBaud
Status (BM) -> 4 = 57.6 kBaud
4.1.2
Gateway Message changed its LRN Mode (RMT Receive Message Telegram)
This telegram is sent by the gateway to the Master after the button
S3 has been pushed. The status of the learning mode is displayed in
the status byte:
Status = 00 -> LRN-Mode is passive
Status = 01 -> LRN-Mode is active, transmitters can be learned into
the input filter.
Bit7 Bit0
SB 1
0xA5
SB 2
0x5A
Typ
8B
ORG
94
DB 3
00
DB 2
00
DB 1
00
DB 0
BM
ID3
No. of the gateway
ID2
No. of the gateway
ID1
No. of the gateway
ID0
No. of the gateway
Status
BM
Chks
Chk-Sum
Bit7 Bit0
SB 1
0xA5
SB 2
0x5A
Typ
8B
ORG
9A
DB 3
00
DB 2
00
DB 1
00
DB 0
00
ID3
No. of the gateway
ID2
No. of the gateway
ID1
No. of the gateway
ID0
No. of the gateway
Status
00, 01
Chks
Chk-Sum