4  First Steps 

 
This section describes the first steps to allow fast commissioning by means of our parameterization 
software:  
 
Starting point: The parameterization software is installed on a PC/notebook and a RS485 network is 
available. The baud rate of the Master and the gateways have been set to the same value.  
 

1.  Connect the gateways to the RS485 bus and turn on the power supply. Make sure that at this 

moment no other gateway with the same user number (TLNR) is connected. LED L1 must 
light up.  
 

2.  First communication test using the parameterization software.  

Try to change the status of LED L5 by means of the buttons Signal_On, Signal_OFF and 
Signal_Flash. If this is possible, correct communication has been established.  
 

3.  Push the radio transmitter. The telegrams must be displayed on the Test tab of the 

parameterization software.  
 

4.  Push the button S3 until LED L3 is flashing. Release the button S3, the gateway switches to 

the learning mode and you have now erased the input filter completely.  
Now learn in a radio transmitter. Each new learned in transmitter ID is indicated by a brief 
flickering of LED L3 and a respective telegram by the Master. As soon as all sensors have 
been learned in, push the button S3 for two seconds to switch back to the normal operation 
mode. L3 goes off.  

 

Changing the user number. The station is now ready for operation. 
 
 
 
 
 
 
 
 
 
 
 
14.06.08 tw/chg 
 

Summary of Contents for 6011000

Page 1: ...ATIO radio bus system Manual RS485 Gateway bidirectional 17 12 2008 Seite 1 19 B chlistrasse 326 CH 8426 Lufingen Phone 41 44 876 00 41 Fax 41 44 876 05 29 info omnio www omnio ch RS485 Gateway bidire...

Page 2: ...1 4 1 5 Gateway Message INFI completely erased RMT Receive Message Telegram 11 4 1 6 Gateway Message INFI full ID not learned RMT Receive Message Telegram 12 4 1 7 Gateway ACK of the last TG RMT Recei...

Page 3: ...cludes two operation modes In the operation mode Direct all received telegrams are sent to the RS485 bus In the operation mode Filter only telegrams of transmitters learned into the gateway will be se...

Page 4: ...All ends of the RS485 network cable including those at stub lines must be terminated by a 120 Ohm resistor This is executed by the setting of jumper J3 on the two outer gateways Communication problems...

Page 5: ...lter If you press the button S3 in the normal operation mode for more than 6 seconds all transmitter ID s in the input filter will be erased LED L3 is flashing If you then release the button S3 the pr...

Page 6: ...ta communication to the RS485 bus active 2 2 2 3 Learning Mode Input Filter LED L3 does not light up normal operation mode is active LED L3 lights up learning mode is active LED L3 is flickering input...

Page 7: ...o gateway by the value 80h Example for 5 gateways Gateway User number 1 FF800000h 2 FF800080h 3 FF800100h 4 FF800180h 5 FF800200h Caution To rule out abuse the user number can be changed max 10 times...

Page 8: ...am from a radio transmitters has been received through the gateway and sent to the RS485 bus The telegram must be acknowledged by the Master Master Gateway 6B TRT Transmit Radio Telegram A telegram fr...

Page 9: ...nnected LED L1 must light up 2 First communication test using the parameterization software Try to change the status of LED L5 by means of the buttons Signal_On Signal_OFF and Signal_Flash If this is...

Page 10: ...ud Status BM 2 19 2 kBaud Status BM 3 38 4 kBaud Status BM 4 57 6 kBaud 4 1 2 Gateway Message changed its LRN Mode RMT Receive Message Telegram This telegram is sent by the gateway to the Master after...

Page 11: ...r which has already been learned in The respective transmitter ID of the learned in transmitter is indicated in the bytes DB3 to DB0 Status IND index pointer 1 32 in the input filter Shows the positio...

Page 12: ...received telegram has been processed successfully 4 1 8 Gateway Replay SW Version RMT Receive Message Telegram This telegram is sent by the gateway to the Master if the received telegram has been pro...

Page 13: ...ode RMT Receive Message Telegram This telegram is sent by the gateway to the Master after the Master has sent an inquiry for the number of already stored transmitter ID s Ind in the input filter DB1 0...

Page 14: ...The user number cannot be changed anymore Status F7 Gateway not in the LRN mode 4 1 14 Gateway Message TRT Buffer is full RMT Receive Message Telegram This telegram is sent by the gateway to the Mast...

Page 15: ...s telegram is sent by the Master to the Gateway after a telegram has been processed successfully by the gateway 4 2 2 Master Get SW Version TCT Transmit Command Telegram Inquiry by the Master to the G...

Page 16: ...mit Command Telegram Inquiry of the current transmitter ID in the input filter of the gateway TLNR by the Master Status Ind Index on storage location in the input filter that is to be read out Possibl...

Page 17: ...ch on LED 5 4 2 8 Master Set new Station Base ID TCT Transmit Command Telegram Inquiry on changing the user number of the gateway Bit7 Bit0 SB 1 0xA5 SB 2 0x5A Typ AB ORG B5 DB 3 00 DB 2 00 DB 1 00 DB...

Page 18: ...DB 3 90 Push Rocker DI Ein DB 3 00 Release Rocker for all Rockers A0 to DI Status 00 By rocker pushed Status 10 By rocker released For example The basis id of the gateway is FFFFFF80h Sends the teleg...

Page 19: ...ctions are part of the device and part of our warranty terms They have to be handed over to the customer The technical specifications of the device may be changed without prior notice The products may...

Reviews: