3.0 SITE PREPARATION AND INSTALLATION
3.1 AC Powered Chassis Site Preparation
Power source should be available within 5 ft. of the chassis and installed per the
National Electrical Code ANSI/NFPA-70.
This equipment requires a 100-240VAC, 0.5Amp, 50/60Hz power outlet. Appropriate
overloading protection should be provided on the AC power source outlets utilized.
The standard operating temperature of this equipment is 0 to 50 degrees C. If
installed in a closed or multi-module rack assembly, the operating ambient
temperature of the rack must not exceed the maximum rated 50 degrees C. See
specifications on page 10 for wide temperature ranges.
Installation of the equipment should be such that the air flow in the front, back
and side vents of the chassis are not compromised or restricted.
Never use this equipment to carry any weight except its own. Never use it as a
shelf to support the weight of other equipment.
3.2 AC Powered Chassis Mounting
Attach the AC power cords to the back of the Power Receptacle and plug into the
AC outlet. Any installed
iConverter
modules will illuminate the power LED.
Fig. 6 Rear of 2-Module Chassis with Power Cord
3.3 DC Powered Chassis Site Preparation
Power source should be available within 5 ft. of the chassis. The over current
protection for connection with centralized DC shall be provided in the building
installation, and shall be a UL listed circuit breaker rated 20 Amps, and installed
per the National Electrical Code, ANSI/NFPA-70.
This equipment requires 18-60VDC/1.0Amp (8235) or 2.0Amp (8236) rated
power. Appropriate overloading protection should be provided on the DC power
source outlets utilized.
WARNING:
Only a DC power source that complies with
safety extra low voltage (SELV) requirements can be
connected to the DC-input power supply.