6 Troubleshooting
6 - 8
CompoNet Communications Unit User’s Manual (I582-E1)
If the configuration of a parameter disables the CompoNet Communications Unit to operate normally,
an error code will be displayed.
The table below shows the errors and the corrective action.
6-3-3
Parameter Setting Error in CompoNet Communications Unit
MX2
Error Codes &
Indicators
RX
Error Codes &
Indicators
Assumed Cause
Corrective Action
One of configuration
parameters P160 to
P167 or P170 to P177
is rejected by inverter.
Check (and correct) the following items:
• Does one of parameters P168, P169, P178, and
P179 contain a value which is not zero?
• Is one of parameters P160 to P167 and P170 to
P177 specifying a Modbus register that does not
exist?
• Is one of parameters P160 to P167 specifying a
double-word Modbus register? If so, are low and
high words specified in sequence by two consec-
utive parameters?
• Is one of parameters P170 to P177 specifying a
double-word Modbus register? If so, are high
and low words specified in sequence by two con-
secutive parameters?
• Is a specific Modbus register specified twice in
output parameters P160 to P167?
• Is one of parameters P160 to P167 specifying a
Modbus register that is read-only?
A register is read-only if it has an "R" in
the R/W column of the register table in
Section 6-8 Modbus Communication
(Modbus-RTU) Data List of the MX2
User's Manual (Cat. No. I570).
A register is read-only if it has an "R" in
the R/W column of the register table in
8-5 Modbus Communication Register
Number List of the RX User's Manual
(Cat. No. I578).
• Is one of parameters P160 to P167 specifying a
Modbus register that is write-prohibited during
operation?
A parameter is write-prohibited during
operation if "no" is put in the "Data can
be changed during RUN" column of the
table in Section 4 of the MX2 Inverter
manual (Cat. No. I570).
A parameter is write-prohibited during
operation if "No" is put in the "Changes
during operation" column of the table in
Section 4 Parameter List of the RX
Inverter manual (Cat. No. I578).
After correcting configuration, cycle the power sup-
ply.
MS
NS
MS
NS
Summary of Contents for 3G3AX-MX2-CRT-E
Page 94: ...3 Network Startup 3 36 CompoNet Communications Unit User s Manual I582 E1...
Page 118: ...4 Remote I O 4 24 CompoNet Communications Unit User s Manual I582 E1...
Page 134: ...5 Message Communications 5 16 CompoNet Communications Unit User s Manual I582 E1...
Page 167: ...I 1 I CompoNet Communications Unit User s Manual I582 E1 Index...
Page 171: ......