Unit dipswitches
fig. 128
/i
fig. 129
The factory setting of all dipswitches is OFF.
ON
1
2
3
4
REGS
NC
ADR
BACK
Dipswitch
Function
Setting
Description
REGS
Create/enable
registration table
ON
Registered table is enabled
OFF
Registered table is disabled
OFF to ON
1
1. When the unit power is on.
Register I/O unit table
ON to OFF
Clear registered I/O unit table
NC
N/A
OFF
Not used, always set to OFF
ADR
Automatic
restore
OFF to ON
When the SmartSlice I/O Units are
replaced, the parameter data that was
backed up with the BACK dipswitch is
automatically restored
2
2. When dipswitch 1 is set to ON.
OFF
Automatic restore disabled
BACK
Backup trigger
ON to OFF to
ON in 3 s
3
3. The setting of dipswitch 4 (BACK) is given in figure 125.
Parameter data of all connected Smart-
Slice I/O Units is backed up
ON
OFF
ON
1 s
1 s
1 s
The backup operation starts after DIP switch 4 is
turned from ON to OFF to ON within 3 seconds.
Caution
The Backup and Restore functionality is available in the GRT1-
ECT. However, the backed up and restored parameters cannot be
accessed via EtherCAT communication.
Note
•
It is recommended to do a registration of the SmartSlice I/O
Units (see the Trajexia Programming Manual).
•
It is recommended to set dipswitches 1 and 3 to on and dip-
switch 4 to off after this registration.