Output Signals
fig. 153
When the option unit interface is enabled, two additional outputs are
available:
When the option unit interface is enabled, the following additional functions
can be allocated to the multi-function outputs (SO1 to SO6):
S-CTRL1 to S-CTRL3 can be controlled by using the
DRIVE_OUTPUTS
parameter in the TJ2-MC__:
SO1
SO1COM
11
10
SO2
SO2COM
ALMCOM
35
34
/ALM
37
36
SO4COM
SO4
39
38
Maximum
service
voltage
: 30 VDC
Maximum
output current
: 50 mADC
ZCOM
Z
19
25
12
40
41
SO5
SO6
SO5&6COM
Pn
number
Parameter
name
Description
Default
setting
Unit Setting
range
Power
supply
OFFto
ON
414
Output Signal
Selection 5
Set the output signal 5
function allocation.
460551 -
0 to
00FFFFFFh
Yes
415
Output Signal
Selection 6
Set the output signal 6
function allocation.
394758 -
0 to
00FFFFFFh
Yes
Signal name
Symbol
Set value
Output terminal that can be allo-
cated
Serial control output 1
S-CTRL1
20h
SO1, SO2, SO4, SO5, SO6
Serial control output 2
S-CTRL2
21h
SO1, SO2, SO4, SO5, SO6
Serial control output 3
S-CTRL3
22h
SO1, SO2, SO4, SO5, SO6
Bit no.
Signal
Description
0
S-CTRL1
Serial control output 1
1
S-CTRL2
Serial control output 2
2
S-CTRL3
Serial control output 3