3 Check and start operation
3-2 Checking the operation
4.
Under this condition, check the unit's LED display and beep sound.
Are they in the same status as shown below?
Status indicator
Beep
None
Power supply output receptacles
Outputs power (connected devices are powered)
If the same as the one shown above:
The operation is normal. Proceed to procedure 5.
If not the same as the one shown above:
The operation is abnormal. "3-4-4 Displays and beeps when there is an equipment failure"
of "3-4 Interpreting beeps and displays" must apply.
Take necessary measures and then proceed to 5.
5.
Disconnect the unit’s AC input from the commercial power. The unit enters Battery
Mode.
6.
In Battery Mode, check the unit's LED display and beep sound.
Does the status indicator appear as one of those shown below? ( indicates blinking)
Status Indicator
Beep
Output
Description
Intermittent
4-second intervals
ON
Backup is operating due to power failure or AC input
error. Output will stop if Battery Mode continues.
Intermittent
1-second intervals
ON
Backup is operating due to power failure or AC input
error. Battery level is low, so output will stop soon.
None
OFF
Battery is dead, so output stopped.
If not the same as one of those shown above:
... Operation is abnormal. Check the status of lamps and beep, and then press the
“Power” switch to turn OFF the power.
・
If the display is one of those shown in “3-4 Interpreting beeps and displays”, take
the necessary measures and then go back to procedure 1.
・
If no Battery Mode is performed and the UPS and the devices connected to the
UPS stop, this may be attributed to an insufficient battery charge.
After connecting the AC input to the commercial power and charging the battery
for at least 8 hours, go back to step 5.
・
If the problem persists after checking the 2 points above, contact us.
BA75T/BA100T/BA100R
42
Summary of Contents for BA100R
Page 23: ...2 Installation and connection 2 1 Installation Incorrect Positions BA75T BA100T BA100R 22...
Page 87: ...8 Note of Chinese 8 Note of Chinese UPS UPS 1 UPS FA OA Windows BA75T BA100T BA100R 86...
Page 88: ...8 Note of Chinese 2 FA OA A VCCI A BA75T BA100T 12 5 BA100R 13 BA75T BA100T BA100R 87 8...
Page 90: ...8 Note of Chinese 5cm AC 25 5 30 4 AC AC AC AC BA75T BA100T BA100R 89 8...
Page 91: ...8 Note of Chinese ON OFF AC INPUT PROTECTION 1mA AC UPS AC UPS BA75T BA100T BA100R 90...
Page 92: ...8 Note of Chinese BA75T BA100T BA100R 91 8...
Page 93: ...8 Note of Chinese AC UPS 25 25 6 40 2 AC AC DC250V BA75T BA100T BA100R 92...
Page 99: ...9 References 9 2 Dimensions Upright stand for BA100R BAP100R BA75T BA100T BA100R 98...
Page 100: ...9 References 9 2 Dimensions Rubber feet BA75T BA100T BA100R 99 9...
Page 101: ...9 References 9 2 Dimensions Using Ear brackets BAP100RS BA75T BA100T BA100R 100...
Page 103: ...9 References 9 4 China RoHS Information 9 4 China RoHS Information BA75T BA100T BA100R 102...