3 Check and start operation
3-3 Start and stop procedures and basic operation
■
Operation when using
You may either leave the “Power” switch of the unit ON (operation status) or turn it OFF
each time when stopping the connected system. Choose whichever operation method is
more convenient.
We recommend turning OFF the “Power” switch when you do not use connected devices
for a long time.
The battery can be charged once the AC input terminal is connected to a commercial
power source.
■
Operation after a power failure
・
If a power failure or abnormal input power supply occurs, the UPS automatically
switches to Battery Mode, continuing power output from the Power Supply Output
Receptacles and output terminal block supplied from the battery.
・
The status is displayed and the beeper sounds intermittently to alert the user.
See also “Setting” switch 1 can be used to turn the beeper ON/OFF.
( indicates blinking)
Icon
Beep
Output
Description
Intermittent
4-second intervals
ON
Backup is operating due to power failure or AC input error.
Output will stop if Battery Mode continues.
Intermittent
1-second intervals
ON
Backup is operating due to power failure or AC input error.
Battery level is low, so output will stop soon.
None
OFF
Battery is dead, so output stopped.
■
Operation when a power failure is recovered
●
When charge of the battery remains
The unit automatically resumes output via commercial power if it recovers from a power
failure/input power supply error while Backup is operating. The spent battery starts
charging.
●
When charge of the battery does not remain
If a power failure or abnormal power input is resolved after the battery is discharged
completely and power output is stopped, the UPS restarts automatically and resumes
power output. The expended battery begins to charge.
BA75T/BA100T/BA100R
45
3
Summary of Contents for BA100R
Page 23: ...2 Installation and connection 2 1 Installation Incorrect Positions BA75T BA100T BA100R 22...
Page 87: ...8 Note of Chinese 8 Note of Chinese UPS UPS 1 UPS FA OA Windows BA75T BA100T BA100R 86...
Page 88: ...8 Note of Chinese 2 FA OA A VCCI A BA75T BA100T 12 5 BA100R 13 BA75T BA100T BA100R 87 8...
Page 90: ...8 Note of Chinese 5cm AC 25 5 30 4 AC AC AC AC BA75T BA100T BA100R 89 8...
Page 91: ...8 Note of Chinese ON OFF AC INPUT PROTECTION 1mA AC UPS AC UPS BA75T BA100T BA100R 90...
Page 92: ...8 Note of Chinese BA75T BA100T BA100R 91 8...
Page 93: ...8 Note of Chinese AC UPS 25 25 6 40 2 AC AC DC250V BA75T BA100T BA100R 92...
Page 99: ...9 References 9 2 Dimensions Upright stand for BA100R BAP100R BA75T BA100T BA100R 98...
Page 100: ...9 References 9 2 Dimensions Rubber feet BA75T BA100T BA100R 99 9...
Page 101: ...9 References 9 2 Dimensions Using Ear brackets BAP100RS BA75T BA100T BA100R 100...
Page 103: ...9 References 9 4 China RoHS Information 9 4 China RoHS Information BA75T BA100T BA100R 102...