3 Check and start operation
3-4 Interpreting beeps and displays
(2) When "Power" switch is "ON"
No.
Status
indicator
Power
supply
output
lamp
Battery
mode
lamp
Battery
replace
ment
lamp
Beep
Charging
Description
Solution
4
None
ON
“Power” switch is ON.
Operating normally.
---
5
None
ON
Battery charge is low, so
the unit is waiting to
start up.
Continue charging the
battery. You can change
the settings with Simple
Shutdown Software.
6
None
ON
Operating normally in
ECO mode.
For details on ECO
mode, refer to "3-1-4
Setting Switch".
3-4-2 Displays and beeps while testing
7
None
OFF
Discharging
Self-diagnostic test in
progress.
---
NOT operation in bypass mode.
3-4-3 Displays and beeps during power failure or AC input
error
(1) When "Power" switch is "ON"
8
Intermittent
4-second
intervals
OFF
Discharging
In Battery Mode due to
power failure or AC
input error. Output will
stop if Battery Mode
continues.
Perform shutdown
operations for the
connected devices and
stop them.
9
Intermittent
1-second
intervals
OFF
Discharging
(Same as above.)
Battery level is low, so
output will soon stop.
(Same as above.)
10
None
OFF
Discharging
Battery is dead, so
output stopped. (This is
displayed only for a few
seconds.)
Charge the battery.
NOT operation in bypass mode.
(2) When "Power" switch is "OFF"
11
None
(ON)
AC input voltage and
AC input frequency are
too high.
Use within the AC input
voltage/frequency range
described in the
specifications.
12
None
(ON)
AC input frequency is
too high.
13
None
(ON)
AC input voltage is too
low and AC input
frequency is too high.
14
None
(ON)
AC input voltage is too
high.
BA75T/BA100T/BA100R
47
3
Summary of Contents for BA100R
Page 23: ...2 Installation and connection 2 1 Installation Incorrect Positions BA75T BA100T BA100R 22...
Page 87: ...8 Note of Chinese 8 Note of Chinese UPS UPS 1 UPS FA OA Windows BA75T BA100T BA100R 86...
Page 88: ...8 Note of Chinese 2 FA OA A VCCI A BA75T BA100T 12 5 BA100R 13 BA75T BA100T BA100R 87 8...
Page 90: ...8 Note of Chinese 5cm AC 25 5 30 4 AC AC AC AC BA75T BA100T BA100R 89 8...
Page 91: ...8 Note of Chinese ON OFF AC INPUT PROTECTION 1mA AC UPS AC UPS BA75T BA100T BA100R 90...
Page 92: ...8 Note of Chinese BA75T BA100T BA100R 91 8...
Page 93: ...8 Note of Chinese AC UPS 25 25 6 40 2 AC AC DC250V BA75T BA100T BA100R 92...
Page 99: ...9 References 9 2 Dimensions Upright stand for BA100R BAP100R BA75T BA100T BA100R 98...
Page 100: ...9 References 9 2 Dimensions Rubber feet BA75T BA100T BA100R 99 9...
Page 101: ...9 References 9 2 Dimensions Using Ear brackets BAP100RS BA75T BA100T BA100R 100...
Page 103: ...9 References 9 4 China RoHS Information 9 4 China RoHS Information BA75T BA100T BA100R 102...