3 Check and start operation
3-4 Interpreting beeps and displays
No.
Status
indicator
Power
supply
output
lamp
Battery
mode
lamp
Battery
replace
ment
lamp
Beep
Charging
Description
Solution
24
Continuous
OFF
Failure occurred. When
the
“
Buzzer
Pause/Test
”
switch is
pressed, the details of
the error are displayed
(No. 26 to 31).
Turn OFF this unit and
all connected devices.
Then, turn the “Power”
switch back ON for this
unit only. If the display
does not change, there
is a problem with this
unit. Contact the shop of
purchase or our
Electronic Systems &
Equipments Customer
Support Center.
25
blinking
---
(Note 2)
Continuous
---
(Note 2)
26
bypass
Continuous
---
(Note 2)
Switched to bypass
operation due to
abnormal rise in output
voltage. (Note 1).
Displays the details of
the error that occurred
only while pressing the
“
Buzzer Pause/Test
”
switch while in state No.
25.
27
bypass
Continuous
---
(Note 2)
Switched to bypass
operation due to
abnormal drop in output
voltage. (Note 1).
(Same as above.)
28
bypass
Continuous
OFF
Stopped charging due
to abnormal rise in
battery charge voltage.
When the battery
discharges, bypass
output is performed.
(The display disappears
completely.)
Displays the details of
the error that occurred
only while pressing the
“
Buzzer Pause/Test
”
switch while in state No.
24.
29
bypass
Continuous
OFF
Stopped charging due
to abnormal drop in
battery charge voltage.
When the battery
discharges, bypass
output is performed.
(The display disappears
completely.)
(Same as above.)
30
bypass
Continuous
---
(Note 2)
Moved to bypass
operation due to
problem with the
internal temperature
(Note 1).
Displays the details of
the error that occurred
only while pressing the
“
Buzzer Pause/Test
”
switch while in state No.
25.
31
bypass
Continuous
---
(Note 2)
Moved to bypass
operation due to
problem with the DC
Bus voltage .(Note 1).
(Same as above.)
32
bypass
Continuous
---
(Note 2)
Moved to bypass
operation due to
problem with the half
wave rectification load
(Note 1) (Note 3)
(Same as above.)
33
Continuous
---
(Note 2)
External Fan Error.
(Same as above.)
BA75T/BA100T/BA100R
49
3
Summary of Contents for BA100R
Page 23: ...2 Installation and connection 2 1 Installation Incorrect Positions BA75T BA100T BA100R 22...
Page 87: ...8 Note of Chinese 8 Note of Chinese UPS UPS 1 UPS FA OA Windows BA75T BA100T BA100R 86...
Page 88: ...8 Note of Chinese 2 FA OA A VCCI A BA75T BA100T 12 5 BA100R 13 BA75T BA100T BA100R 87 8...
Page 90: ...8 Note of Chinese 5cm AC 25 5 30 4 AC AC AC AC BA75T BA100T BA100R 89 8...
Page 91: ...8 Note of Chinese ON OFF AC INPUT PROTECTION 1mA AC UPS AC UPS BA75T BA100T BA100R 90...
Page 92: ...8 Note of Chinese BA75T BA100T BA100R 91 8...
Page 93: ...8 Note of Chinese AC UPS 25 25 6 40 2 AC AC DC250V BA75T BA100T BA100R 92...
Page 99: ...9 References 9 2 Dimensions Upright stand for BA100R BAP100R BA75T BA100T BA100R 98...
Page 100: ...9 References 9 2 Dimensions Rubber feet BA75T BA100T BA100R 99 9...
Page 101: ...9 References 9 2 Dimensions Using Ear brackets BAP100RS BA75T BA100T BA100R 100...
Page 103: ...9 References 9 4 China RoHS Information 9 4 China RoHS Information BA75T BA100T BA100R 102...