3 Check and start operation
3-4 Interpreting beeps and displays
Note 1: In bypass operation, commercial power is output directly. Output stops when a power failure
(AC input OFF) occurs in bypass operation.
Note 2: The displays and operations vary according to the status.
Note 3: Devices such as dryers, some solenoid valves, etc., which have a half-wave rectifier.
(2) When "Power" switch is "OFF"
No.
Status
indicator
Power
supply
output
lamp
Battery
mode
lamp
Battery
replace
ment
lamp
Beep
Charging
Description
Solution
34
Continuous
OFF
Failure occurred. When
the
“
Buzzer
Pause/Test
”
switch is
pressed, the details of
the error are displayed.
There is a problem with
the unit. Contact the
shop of purchase or the
OMRON Electronic
Systems & Equipments
Customer Support
Center.
35
Continuous
OFF
Stopped charging due
to abnormal rise in
battery charge voltage.
Turn off AC input.
36
Continuous
OFF
Stopped charging due
to abnormal drop in
battery charge voltage.
(Same as above.)
3-4-5 Display and beep for battery replacement
37
Intermittent
2.0-second
intervals
ON
The self-diagnosis test
detected a weak battery
(warning only, output
continues).
Replace the battery.
You can replace the
weak battery with a
separately purchased
replacement battery as
needed.
See also “4-2 Replacing
the battery”.
38
Intermittent
2-second
intervals
ON
Battery life counter went
off-scale. (Warning only.
Outputs continue.)
39
---
---
---
None
OFF
Battery life counter has
been reset.
Be sure to reset the
battery life counter after
replacing the battery.
See also “4-2 Replacing
the battery”.
BA75T/BA100T/BA100R
50
Summary of Contents for BA100R
Page 23: ...2 Installation and connection 2 1 Installation Incorrect Positions BA75T BA100T BA100R 22...
Page 87: ...8 Note of Chinese 8 Note of Chinese UPS UPS 1 UPS FA OA Windows BA75T BA100T BA100R 86...
Page 88: ...8 Note of Chinese 2 FA OA A VCCI A BA75T BA100T 12 5 BA100R 13 BA75T BA100T BA100R 87 8...
Page 90: ...8 Note of Chinese 5cm AC 25 5 30 4 AC AC AC AC BA75T BA100T BA100R 89 8...
Page 91: ...8 Note of Chinese ON OFF AC INPUT PROTECTION 1mA AC UPS AC UPS BA75T BA100T BA100R 90...
Page 92: ...8 Note of Chinese BA75T BA100T BA100R 91 8...
Page 93: ...8 Note of Chinese AC UPS 25 25 6 40 2 AC AC DC250V BA75T BA100T BA100R 92...
Page 99: ...9 References 9 2 Dimensions Upright stand for BA100R BAP100R BA75T BA100T BA100R 98...
Page 100: ...9 References 9 2 Dimensions Rubber feet BA75T BA100T BA100R 99 9...
Page 101: ...9 References 9 2 Dimensions Using Ear brackets BAP100RS BA75T BA100T BA100R 100...
Page 103: ...9 References 9 4 China RoHS Information 9 4 China RoHS Information BA75T BA100T BA100R 102...